Customization: | Available |
---|---|
After-sales Service: | Lifetime Technical Support |
Warranty: | 1 Year for Three Phase Relay Tester |
Still deciding? Get samples of US$ 2900/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Introduction:
Large LCD Relay Test Set Three Phase Relay Tester with PC Software is applied to test the relay unit in relay protection system. At the same time it could be considered as a universal three phase AC/DC voltage source or current source.
Large LCD Relay Test Set Three Phase Relay Tester with PC Software is applied to test protection replay based on voltage and current operation.
The main function of the tester include: calibration of voltage and current operation relays, secondary circuit inspection,trip value of circuit breaker test, switch on and off time measurement of circuit breaker and so on.
It's a low cost, simple operation and reliable performance device for secondary circuit test.
No. | Items | Specifications | |||||
Alternating Current(AC) output | |||||||
1 | Output accuracy | 0.5magnitude | |||||
2 | Phase current output (effective value) | 0~40A | |||||
3 | Three parallel phase current output (effective value) | 0~120A | |||||
4 | Phase current value with long time under permission (effective value) | 10A | |||||
5 | Phase current maximum power output | 420VA | |||||
6 | Three parallel phase current maximum power output | 900VA | |||||
7 | Three parallel phase current maximum work time | 10s | |||||
8 | Frequency range (base wave) | 20~1000Hz | |||||
9 | Harmonic frequency number | 1~20 time | |||||
Direct Current(DC) output | |||||||
1 | Output accuracy | 0.5magnitude | |||||
2 | Current output | 0 ~ ± 10 A/each phase 0 ~ ± 30 A/every three parallel |
|||||
3 | Maximum output of load voltage | 20v | |||||
Alternating Voltage output | |||||||
1 | Output accuracy | 0.5magnitude | |||||
2 | Phase voltage output (RMS) | 0 ~ 120v | |||||
3 | Line voltage output (RMS) | 0 ~ 240v | |||||
4 | Phase voltage/line voltage power output | 80VA/100VA | |||||
5 | Frequency range (base wave) | 20 ~ 1000Hz | |||||
6 | Harmonic frequency number | 1 ~ 20 times | |||||
Direct voltage output | |||||||
1 | Output accuracy | 0.5magnitude | |||||
2 | Phase voltage output amplitude | 0 ~ +160v | |||||
3 | Line voltage output amplitude | 0 ~ + 320v | |||||
4 | Phase voltage/line voltage power output | 70VA/140VA | |||||
The switch quantity and time measurement | |||||||
1 | Switch parameters input | 7 ways; Empty contact: 1~20mA, 24v Power contact access: "0":0~ +6V; "1":+11 V ~ +250V |
|||||
2 | Switch parameters output | 2 couples DC:220V/0.2A; AC:220V/0.5A | |||||
3 | Time measurement | Measuring range: 0.1ms ~ 9999s / 0.1ms |