Customization: | Available |
---|---|
After-sales Service: | Lifetime Technical Support,Online Service |
Warranty: | 1 Year for IR Tester |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Description:
The digital insulation resistance tester has a built-in real-time industrial microcomputer operating system, a built-in ultra-thin linear meter head and a dot matrix LCD display. It is an ideal insulation resistance test equipment for measuring large-capacity transformers, mutual inductors, generators, high-voltage motors, power capacitors, power cables, lightning arresters, etc.
Large capacity, strong anti-interference, pointer and digital synchronous display, AC and DC dual-use, simple operation, automatic calculation of various insulation indicators (absorption ratio, polarization index), all measured characteristics have anti-power-off function.
Features:
1.The insulation resistance is displayed in two ways at the same time: the pointer type can easily observe the variation range of the insulation resistance; the digital type displays the measurement results accurately.
2.High degree of automation, strong anti-interference ability, the instrument can automatically calculate the absorption ratio and polarization index without manual intervention
3.Friendly interface, all measurement results have anti-power-off function, and can store 19 continuous measurement values
4.The instrument generates high voltage and has tone output
5.Built-in residual high voltage discharge circuit, which can automatically discharge the residual pressure on the tested equipment after the test is completed
Specifications:
1.Measuring range and accuracy
(Temperature, humidity: 23±5ºC, 45~75%RH)
Model |
GD2306 |
|
Rated Voltage |
5000V |
10000V |
Measuring Range |
0.0~99.9MΩ 100~999MΩ 1.00~9.99GΩ 10.0~99.9GΩ 100~200GΩ |
0.0~99.9MΩ 100~999MΩ 1.00~9.99GΩ 10.0~99.9GΩ 100~400GΩ |
Open circuit Voltage |
DC 5000V +20%, -0% |
DC 10000V +10%, -0% |
Short-circuit Current |
Approx 3.3mA |
Operating system | Dual integration |
Display | Liquid crystal display (Max. 9999counts) Bar graph / Max. 31points |
Low battery warning | Battery mark display (in 4 levels) |
Over range indication | "----" mark appears on insulation resistance range. |
Sample rate | approx 0.5~5 times/sec |
Operable altitude | 2000m or less above sea level |
Insulation resistance | 1000MΩ or more /DC 1000V (Between electrical circuit and enclosure) |
Dimension | 230(L) ×190(W) ×90(D) mm |
Weight | approx 3.5kg (battery included) |
Power source | DC15V/4A Adapter Power Or DC9.6V: charging battery size AA×8pcs |
Accessories: