Customization: | Available |
---|---|
After-sales Service: | Lifetime Technical Support,Online Service |
Warranty: | 1 Year |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
1.AC current source:
Current range: 6x (0~30A)/phase, accuracy 0.5%.
6 phase parallel current output: 180A
Phase current working value for allowed long time: 10A
Power: 300VA/phase
Maximum output power of 6 phases in parallel: 900VA
Maximum permitted work time of 6 phases in parallel: 10S
Frequency range: 0~1000Hz; accuracy: 0.001Hz
Harmonic time: 2~20; phase: 0--360°; accuracy: 0.1°
2.DC current source:
Current range: 20A / phase, power: 300VA/phase, accuracy:0.5%
3.AC voltage source:
Phase voltage output:6x( 0~125V)/phase, accuracy: 0.5%
Line voltage output: 0~250V
Phase voltage / Line voltage output power: 70VA / 100VA
Frequency range: 0~1000Hz accuracy: 0.001Hz
Harmonic time: 2~20; phase: 0--360°; accuracy: 0.1°
4.DC voltage source:
Phase voltage output range: 0~±150V accuracy: 0.5%
Line voltage output range: 0~±300V
Phase voltage / Line voltage output power: 90VA / 180VA
5.Switch terminal:
Switch input terminals: 8 pairs
Dead contact: 1-20mA, 24V active output inside the device.
Potential flip: 0--6V DC low level
15-250V DC high level
Switch output terminals: 4 pairs, dead contact, rupturing capacity: 110V/2A, 220V/1A
6.Time measurement range:
Range: 1ms-9999s; accuracy: 1ms
Software: