Three Phase transformer turn ratio meter Z Connect TTR Testing equipments
What is application about transformer turns ratio meter test?
The transformer turns ratio meter test is used to determine the number of turns in one winding of a transformer in relation to the number of turns in the other windings of the same phase of the transformer. The transformer polarity test determines the vectoral relationships of the various transformer windings
Item Name | GDB-D Z Type Three Phase Transformer Turns Ratio Meter |
Turns ratio range | 0.8-10000 |
Group testing range | 1~12 |
Turns ratio accuracy | 0.2% (180V: 0.8~1000 |
)0.5% (180V: 1000~10000) | |
0.2%( 0.8~200) | |
Turns ratio resolution | 0.0001 |
Power input | 220V±10% 50HZ±1Hz |
Working temperature | -20ºC~40ºC |
Relative humidity | ≤85% no condensation |
Dimension | 325mm×278mm×188 mm |
Weight | 7kg |
Applicable to transformer | Connected in Y type, D type and Z type |
Phase measurement erro | 1 degree |
Test voltage | 0~180V |
Communication | Upload the test results to PC by USB port and make word report by software |
Printing | Print the test results by micro printer |