Abstract:
Characteristics:
♦ Apply to all types of metal contacts used in SF6 switches, GIS combination appliances, vacuum switches, and oil switches made domestically and abroad.
♦ Easy to install linear travel sensor and rotating sensor.
♦ Display all data and waveforms on the host's large clear, backlit LCD screen with electric contrast control.
♦ Host can save the test results for opening and shutting for several groups. It is simple to record and store the test date and time thanks to the embedded real-time clock.
♦ Print all data and the map using the integrated rapid micro printer.
♦ With a powerful data analysis function, it is able to examine each mechanical feature of a circuit breaker.
Technique Parameters:
12 channels for time measurement |
3-channel supports both the time contact and resistance contact time 6-channel isolated contacts for cascaded unit measurement of pole |
Time measurement | Range: 4000ms Error :< 0.1ms Resolution: 0.01ms Linear resistance sensor: |
Travel measurement according to sensor |
Linear resistance sensor Measurement range: 0~250mm; resolution: 0.01mm; error:<0.5mm Measurement range: 0~25mm; resolution: 0.01mm; error:<0.05mm Angle resistance sensor: Measurement range: 0~360°; resolution: 0.01°; error:<0.5° |
Pre-insertion Resistance Measurement |
Range: 50~5000ohm; error :<1%RDG+2D |
Dynamic resistance measurement |
Test current: 25~100A Measurement error :< 1%RDG+2D |
Contact resistance measurement |
Range:0--10mohm ; Error<0.5%RDG+0.05%FS Range: 0-2mohm; Error:<0.5%RDG+2D |
Speed measurement | 250mm linear resistance scale: 0~20m/s; error:<0.5%RDG+2D 25mm linear resistance scale: 0~20m/s; error:<0.5%RDG+2D Angle sensor: 0~20m/s; error:<0.5%RDG+2D Acceleration sensor: 0~20m/s; error:<5%RDG+2D |
Coil current measurement | Range: 0~20A; resolution: 0.001A; error:<0.01A |
Vibration measurement | Range: 0~5000G; error:<3% |
Internal DC power source | Voltage: 12~265V; current:0~20A |
Data Save | Built-in 8G storage memory and 2 USB interface for data export and external keyboard or mouse connection |
Power supply | AC220V±10%; 50Hz±10% |
Working environment | Temperature: -10~50°C; Humidity:<80% |
Display of Air Circuit Breaker Mechanical Characteristic Tester: