1. GDMZ Precision Capacitance and Tan Delta Dissipation Tester is used to measure dissipation factor (PF) in heavy interference site such as power plants or power substations. It can also be used in laboratory for high accurate test.
1 | Condition of Use | -5°C~40°C, RH<80% |
2 | Power Source | AC 110V±10% Without Frequency Limit |
3 |
High Voltage Output |
Range:1KV~10KV, every 1KV |
Precision:5% | ||
Maximum Current:140mA | ||
Capacity:1000VA | ||
4 |
Self-Excited Power |
Voltage Range:AC0-30V |
Frequency:45Hz/55Hz | ||
Maximum Current:15A | ||
5 |
Definition |
tgδ: 0.001% ; Cx: 0.1PF |
6 |
Accuracy |
tgδ:±(reading*1.0%+0.040%) |
Cx:±(reading*1.0%+1.0pF) | ||
7 | Measuring Range | tgδ: Without Limit |
Cx:15pF<Cx<100000pF | ||
10KV:Cx<30000pF | ||
5KV:Cx<60000pF | ||
1KV:Cx<100000pF | ||
CVT Test:Cx<100000pF | ||
8 | Size | 470mm(L) ×320mm(W)×390mm(H) |
9 | Weight | 30kg |