Customization: | Available |
---|---|
After-sales Service: | Lifetime Technical Support |
Warranty: | 1 Year for Secondary Current Injection Test Set |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
The instrument is applied to test the relay unit in relay protection system. At the same time it could be considered as a universal three phase AC/DC voltage source or current source.
It is applied to test protection replay based on voltage and current operation.
The main function of the tester include: calibration of voltage and current operation relays, secondary circuit inspection,trip value of circuit breaker test, switch on and off time measurement of circuit breaker and so on.
It's a low cost, simple operation and reliable performance device for secondary circuit test.
Specifications:
Alternating Current(AC) output | |||
1 | Output accuracy | 0.5magnitude | |
2 | Phase current output (effective value) | 0~40A | |
3 | Three parallel phase current output (effective value) | 0~120A | |
4 | Phase current value with long time under permission (effective value) | 10A | |
5 | Phase current maximum power output | 420VA | |
6 | Three parallel phase current maximum power output | 900VA | |
7 | Three parallel phase current maximum work time | 10s | |
8 | Frequency range (base wave) | 20~1000Hz | |
9 | Harmonic frequency number | 1~20 time | |
Direct Current(DC) output | |||
1 | Output accuracy | 0.5magnitude | |
2 | Current output | 0 ~ ± 10 A/each phase 0 ~ ± 30 A/every three parallel |
|
3 | Maximum output of load voltage | 20v | |
Alternating Voltage output | |||
1 | Output accuracy | 0.5magnitude | |
2 | Phase voltage output (RMS) | 0 ~ 120v | |
3 | Line voltage output (RMS) | 0 ~ 240v | |
4 | Phase voltage/line voltage power output | 80VA/100VA | |
5 | Frequency range (base wave) | 20 ~ 1000Hz | |
6 | Harmonic frequency number | 1 ~ 20 times | |
Direct voltage output | |||
1 | Output accuracy | 0.5magnitude | |
2 | Phase voltage output amplitude | 0 ~ +160v | |
3 | Line voltage output amplitude | 0 ~ + 320v | |
4 | Phase voltage/line voltage power output | 70VA/140VA | |
The switch quantity and time measurement | |||
1 | Switch parameters input | 7 ways;Empty contact: 1~20mA, 24v Power contact access: "0":0~ +6V; "1":+11 V~ +250V |
|
2 | Switch parameters output | 2 couples DC: 220V/0.2A; AC: 220V/0.5A | |
3 | Time measurement | Measuring range: 0.1ms ~ 9999s / 0.1ms |