TTR Testing Equipment Portable Power Transformer Turn Ratio Meter

Product Details
Customization: Available
Ratio Measurement Range: 1-10000
Group Measurement: 1-12
Diamond Member Since 2007

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

Registered Capital
100800000 RMB
Plant Area
>2000 square meters
  • TTR Testing Equipment Portable Power Transformer Turn Ratio Meter
  • TTR Testing Equipment Portable Power Transformer Turn Ratio Meter
  • TTR Testing Equipment Portable Power Transformer Turn Ratio Meter
  • TTR Testing Equipment Portable Power Transformer Turn Ratio Meter
  • TTR Testing Equipment Portable Power Transformer Turn Ratio Meter
Find Similar Products

Basic Info.

Model NO.
GDBC-901
Test Voltage
0~80V, Frequency 50Hz
Power Supply
AC220V ± 10%, 50Hz/60Hz
Environment Temperature
0-50°c
Humidity
≤85%R
Weight
22kg
Transport Package
Wooden Box
Specification
58*45*36CM
Trademark
GOLD
Origin
China
Production Capacity
500sets/Month

Product Description

TTR testing equipment Portable Power Transformer Turn Ratio Meter

TTR Testing Equipment Portable Power Transformer Turn Ratio Meter

GDBC-901
TTR testing equipment Portable Power Transformer Turn Ratio Meter could be applied to test the turns ratio and group vector of single or three phase transformer. Also the connection group of transformer could be calculated with the ratio. All parameters are measured in one test for three phase transformer. 

 

Introduction

  • GDBC-901 Three Phase Transformer Turns Ratio TTR Tester is designed according IEC76-1 and IEC60044. 
  • The voltage ratio measurement for three or singe phase transformer.
  • The group vector measurement for three phase transformer.
  • The polarity measurement for single phase transformer or CT/PT.
  • Voltage ratio error calculation.
  • Current transformer ratio measurement.
  • Excitation current measurement in ratio testing.
  • Reproduction the AC test voltage from power source to reduce the effects of bad power source.
  • Save the test results in the memory internal the tester.
  • Print the test results by micro printer.
  • Reverse connection detect unit to prevent the high voltage injected to operator.
  • Over current protection unit integrated in software and hardware.
  • Upload the test results to PC by RS232 and make word report by software.

Specifications:

1 Item Name GDBC-901 Single Phase and Three Phase Transformer Turns Ratio TTR Tester
2 Ratio measurement range 1-10000
3 Group measurement 1-12
4 Phase measurement error 1 degree
5 Ratio measurement error 1-2000 ± 0.2%RDG   2000-10000  ± 0.5%RDG
6 Test voltage 0~80V, frequency 50Hz
7 Power supply AC220V ± 10%, 50Hz/60Hz
8 Environment temperature 0-50°C
9 Humidity ≤85%R
10 Dimension 58*45*36CM
11 Weight 22Kg


TTR Testing Equipment Portable Power Transformer Turn Ratio Meter

Precautions:

  1. Insurance 1 is 2A, insurance 2 is 0.5A. If the test lead is short-circuited, the high and low voltages are  reversed, and the fuse will be blown. After the fuse is blown out, if you take a measurement, it will stop after displaying "Measuring, please wait!". Please shut down, replace the insurance with the same capacity, and retest.
  2. Keep good contact during wiring. The instrument should be well grounded.
  3. The working place of the instrument should be far away from strong electric field, strong magnetic field and high-frequency equipment. The smaller the power supply interference, the better. The lighting cable should be used. If the power supply interference is still large, the instrument can be powered by the AC purification power supply. The capacity of the AC purification power supply can be greater than 200VA.
  4. When the instrument is working, if the LCD display is disordered, all the keys have no response, or the measured value is far from the actual value, please press the reset key, or turn off the power, and then restart the operation.
  5. The display has no characters, or the color is very light. Please adjust the brightness potentiometer to a suitable position. The brightness potentiometer is a multi-turn potentiometer with 10 turns.
  6. The instrument should be stored in a dry and ventilated place. If it is not used for a long time or the environment is humid, the preheating time should be extended to remove moisture.
  7. Used for communication port debugging.

About Us

CHONGQING GOLD MECHANICAL & ELECTRICAL EQUIPMENT CO., LTD

Chongqing Gold Mechanical & Electrical Equipment Co.,Ltd.  mainly design and manufacture the oil purifier and electrical testing equipment for more than 10 years.

After several years' development, our products have become high intelligent and wide coverage. And our company has become one of the leading manufacturer of oil purifier and electrical testing equipment in China;

We have developed sales channels in many countries such as UAE, Saudi Arabia, Iran, Malaysia, Thailand, Pakistan, India, Germany, Belgium, USA, Mexico, Kenya, Nigeria, South Africa and other countries worldwide.

And we have gained strong advantage and high reputation in international market.

We have persisted on the business idea of "Integrity Basis and Quality First" for the stable and constant development. We are making effort to develop together with customers from both domestic and abroad on the basis of reciprocity. Client, quality and service are our supreme target!

 

FAQ
  • What's the delivery lead time?

"For most of the products, delivery lead time is 10 days after the order is confirmed; For some customized products, please check with the sales person."

  • What's the payment term?

"For total amount below USD3,000.0, payment term is 100% T/T as deposit; For total amount above USD3,000.0, payment term is 30% T/T as deposit, the balance before delivery; The payment term is also negotiable."

  • What's the warranty period?

"Warranty period is 1 year"