Customization: | Available |
---|---|
After-sales Service: | Lifetime Technical Support,Online Service |
Warranty: | 1 Year for Circuit Breaker Analyzer |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
GDGK-306A High Voltage Circuit Breaker Tester takes the ARM7 unit for core to sample, process and output; the main characteristic is that it's operated in alt.
GDGK-306A High Voltage Circuit Breaker Tester has many advantages such as intelligence, multi-functional, accurate data, strong anti-jamming, easy operation, small size, light weight ,beautiful appearance, etc;
GDGK-306A High Voltage Circuit Breaker Tester can test the circuit breakers as follows: indoors or outdoors circuit breakers with less oil or more oil, vacuum circuit breakers, SF6 circuit breakers and so on.
Contacts' closing time and opening time;
Re-closing time;
Opening or closing's asynchronism;
Springing time or springing times;
Clearance between open contacts/gaps, over-travel, over-shoot and springback;
Speed at instant of contacts touching (separating);
Opening (Closing) max speed;
Opening (Closing) average speed;
Display and Print V-S curve
Operating current curve;
Closing resistance measurement
Large color screen in touch operating
Specifications:
1 |
Time |
Simultaneity measure Contacts | ≤12 |
Range | 0-6s | ||
Resolution | 0.01ms | ||
2 |
Travel |
Range | < 250mm |
Resolution | 0.01mm | ||
3 |
Error |
Time measurement | ±0.5% |
Travel measurement | ±1mm | ||
4 | Speed | Measure range | 0-20m/s |
5 |
Internal Power |
Output Voltage | 30V-260V |
Error | 1% | ||
Output Current | 0~10A | ||
6 |
Power Supply |
Power Supply | AC220V±10 %, 50Hz |
Power dissipation | ≤60w | ||
7 |
Working Environment |
Ambient temperature | 0~40°C |
Humidity | ≤90%RH | ||
8 |
Size |
Dimension | 54*46*56CM |
Weight | 31Kg |