• High Voltage CB Analyzer Circuit Breaker Analyzer Circuit Opening Time Test
  • High Voltage CB Analyzer Circuit Breaker Analyzer Circuit Opening Time Test
  • High Voltage CB Analyzer Circuit Breaker Analyzer Circuit Opening Time Test
  • High Voltage CB Analyzer Circuit Breaker Analyzer Circuit Opening Time Test
  • High Voltage CB Analyzer Circuit Breaker Analyzer Circuit Opening Time Test
  • High Voltage CB Analyzer Circuit Breaker Analyzer Circuit Opening Time Test

High Voltage CB Analyzer Circuit Breaker Analyzer Circuit Opening Time Test

After-sales Service: Lifetime Technical Support,Online Service
Warranty: 1 Year for Circuit Breaker Analyzer
Time Simultaneity Measure Contacts: ≤12
Time Range: 0—6s
Time Resolution: 0.01ms
Travel Range: < 250mm
Customization:
Diamond Member Since 2007

Suppliers with verified business licenses

Manufacturer/Factory, Trading Company
  • Overview
  • Company Profile
Overview

Basic Info.

Model NO.
GDGK-306A
Travel Resolution
0.01mm
Time Measurement Error
±0.5%
Travel Measurement Error
±1mm
Speed Measure Range
0—20m/S
Internal Output Voltage
30V—260V
Power Supply
AC220V±10 %, 50Hz
Transport Package
Standard Wooden Case
Specification
31kg
Trademark
GOLD
Origin
Chongqing, China (Mainland)
HS Code
9031809090
Production Capacity
200pieces/Month

Product Description

High Voltage CB Analyzer Circuit Breaker Analyzer Circuit Opening Time Test

High Voltage CB Analyzer Circuit Breaker Analyzer Circuit Opening Time Test

High Voltage CB Analyzer Circuit Breaker Analyzer Circuit Opening Time Test
 

Introduction:

  • GDGK-306A High Voltage Circuit Breaker Tester takes the ARM7 unit for core to sample, process and output; the main characteristic is that it's operated in alt.

  • GDGK-306A High Voltage Circuit Breaker Tester has many advantages such as intelligence, multi-functional, accurate data, strong anti-jamming, easy operation, small size, light weight ,beautiful appearance, etc;

  • GDGK-306A High Voltage Circuit Breaker Tester can test the circuit breakers as follows: indoors or outdoors circuit breakers with less oil or more oil, vacuum circuit breakers, SF6 circuit breakers and so on.

     

Major testing items and functions:

  • Contacts' closing time and opening time;

  • Re-closing time;

  • Opening or closing's asynchronism;

  • Springing time or springing times;

  • Clearance between open contacts/gaps, over-travel, over-shoot and springback;

  • Speed at instant of contacts touching (separating);

  • Opening (Closing) max speed;

  • Opening (Closing) average speed;

  • Display and Print V-S curve

  • Operating current curve;

  • Closing resistance measurement

  • Large color screen in touch operating

 

Specifications:

 

 

 

1

 

 

Time

Simultaneity measure Contacts ≤12
Range 0-6s
Resolution 0.01ms

 

2

 

Travel

Range < 250mm
Resolution 0.01mm

 

3

 

Error

Time measurement ±0.5%
Travel measurement ±1mm
4 Speed Measure range 0-20m/s

 

 

5

 

 

Internal Power

Output Voltage 30V-260V
Error 1%
Output Current 0~10A

 

6

 

Power Supply

Power Supply AC220V±10 %, 50Hz
Power dissipation ≤60w

 

7

 

Working Environment

Ambient temperature 0~40°C
Humidity ≤90%RH

 

8

 

Size

Dimension 54*46*56CM
Weight 31Kg
High Voltage CB Analyzer Circuit Breaker Analyzer Circuit Opening Time Test
Company Profile

High Voltage CB Analyzer Circuit Breaker Analyzer Circuit Opening Time TestHigh Voltage CB Analyzer Circuit Breaker Analyzer Circuit Opening Time TestHigh Voltage CB Analyzer Circuit Breaker Analyzer Circuit Opening Time TestHigh Voltage CB Analyzer Circuit Breaker Analyzer Circuit Opening Time Test

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now

You Might Also Like

Diamond Member Since 2007

Suppliers with verified business licenses

Manufacturer/Factory, Trading Company
Registered Capital
100800000 RMB
Plant Area
>2000 square meters