Introduction:
Functions:
1 Breakdown test of user-defined |
2 Proof test |
3 Calibration interface for customers |
4 Unloading data to PC and making word report automatically. |
5 Result print |
Specifications:
1 | Output voltage | AC 0~80KV/AC 0~100KV |
2 | Rate of voltage rise | 2KV/s±10% |
3 | Measuring precision | 3%RDG+0.3%FS |
4 | Test times setting | 1~9 |
5 | Mixing time setting | 0~99 second |
6 | Waiting time setting | 0-9 minute 59second |
7 | Maximum storage capacity | 100 groups of test data |
8 | Test standards | IEC60156 |
9 | Display | 256*128 LCD |
10 | Rated power supply | AC 220V±10% 50Hz/60Hz |
11 | Environment temperatures | 0-50°C |
12 | Relative humidity | ≤80%RH |
13 | Size | 420×380×410mm3 |
14 | Weight | 28kg |