Customization: | Available |
---|---|
After-sales Service: | Yes |
Warranty: | 1 Year for Transformer CT PT CVT Analyzer Current |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Transformer CT PT CVT Analyzer Current Transformer Test Set
Applications of CT/ PT Analyzer:
1. CT nameplate check
2. CT parameters check in work burden
3. CT transient parameters analysis
4. CT ratio and phase error calibration
5. PT routine test
GDVA-405 CT PT Analyzer | ||
1 | Test standards | IEC60044-1, IEC60044-6, GB1208, GB16847, C57.13 |
2 | Power supply | AC220V±10%,50Hz/60Hz±10% |
3 | Power output | 0.1~125V (AC) |
4 | Current output | 0.001~5A(RMS) |
5 | Power output | 300VA |
6 | Max. knee voltage measurement | 45kv |
7 | Current measurement range | 0~10A (automatically change range in 0.1/0.4/2/10A) |
8 | Current measurement error | <±0.1%+0.01%FS |
9 | Voltage measurement range | 0~200 V (automatically change range in 1V/10V/70V/200V) |
10 | Voltage measurement error | < ±0.1%+0.01%FS |
11 | Turns ratio measurement range | 1~30000; 1~2000 error<0.05%; 2000~5000 error>0.1%; 5000~35000 error<0.2% |
12 | Phase measurement | error:±2min,resolution:0.01min |
13 | Coil resistance measurement | Range: 0~8kΩ(automatically change range in 2ohm /20ohm /80ohm/800ohm/8kohm) Error< 0.2%RDG+0.02%FS Maximum resolution: 0.1mΩ |
14 | Temperature measurement | -50~100 Celsius degree, error<3 Celsius degree |
15 | CT Secondary burden | Range 0-160ohm (automatically change range in 2ohm/ 20ohm/80ohm/160ohm) Error <0.2%RDG+0.02%FS Maximum resolution 0.001ohm |
16 | PT Secondary burden | Range 0-80kohm (automatically change range in 800ohm / 8kohm /80kohm) Error <0.2%RDG+0.02%FS Maximum resolution: 0.1ohm |
17 | PT ratio measurement | Range: 1~30000, 1~5000 error<0.2% 5000~30000 error<0.5% |
18 | Saved data groups | >1000groups |
19 | Work condition | Temperature:-10ºC-50ºC, moist:≤90% |
20 | Size | 70*50*41CM |
21 | Weight | 40kg |
Name | Quantity | Description |
Host machine | 1 | |
3M mask cable | 2 | Test cable for power out and CT secondary connection |
10M mask cable | 1 | Test cable for CT primary connection |
Grounding cable | 1 | |
Big test pliers | 2 | One red and one black |
Test gasket | 4 | Two red and two black |
Test pin | 4 | Two red and two black |
Test pliers | 12 | Three red and nine black |
Short connection cable | 1 | Including six connection terminals |
3A fuse | 3 | |
Power cable | 1 | |
Accessories bag | 1 | |
Production disk | 1 | Include Analysis application and user manual |
User manual | 2 | |
Inspection report | 1 | |
Pass certificate | 1 |