Customization: | Available |
---|---|
After-sales Service: | Lifetime Technical Support |
Warranty: | 1 Year for Transformer Oil Bdv Tester |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
1. During routine test of power transformer maintenance, check the frequency response data of transformer winding
2. When the power transformer leaves the factory, measure the winding frequency response data of the transformer as the characteristic fingerprint information of the transformer
Sweeping frequency method to measure winding deformation | |
Scan frequency range |
10HZ-1MHZ (DLT911-2016 0.5KHZ interval linear scan) 20HZ-2MHZ (GB/T-1094.18 IEC60076-18:2012 segmented scanning) 10HZ-10MHZ (GB/T-1094.18 IEC60076-18:2012 segmented scanning) 1KHZ -1000KHZ_1.0(Linear scan 1KHZ interval PC side available) 1KHZ -1000KHZ_0.5(linear scan 0.5KHZ interval avaiable for Pc) 1KHZ -2000KHZ_1.0(linear scan 1KHZ interval available for PC) 1KHZ -2000KHZ_0.5(linear scan 0.5KHZ interval available for PC)
100HZ-1000K(Segmented scan PC available 1441 points): 100HZ-1KHZ 5HZ interval 180 points 1KHZ-10KHZ 50HZ interval 180 points 10KHZ-100KHZ 500HZ interval 180 points 100KHZ-1000KHZ 1KHZ interval 901 points
100HZ-2000K(Segmented scan PC available 2441 points): 100HZ-1KHZ 5HZ interval 180 points 1KHZ-10KHZ 50HZ interval 180 points 10KHZ-100KHZ 500HZ interval 180 points 100KHZ-1000KHZ 1KHZ interval 900 points 1000KHZ-2000KHZ 1KHZ interval 1001 Points |
Amplitude measurement range |
(-100dB) - (+20dB) |
Amplitude measurement accuracy |
(-40dB) - (+20dB) 0.2dB (-60dB) - (-40dB) 0.5dB (-80dB) - (-60dB) 1.0dB |
Angle measurement range |
(-180°) - (+180°) (10HZ-2MHZ) |
Scan frequency accuracy |
less than 0.01% |
Signal input impedance |
greater than 1M Ω(DLT911-2016). 50 Ω(GB/T-1094.18 IEC60076-18:2012) |
Signal output impedance |
50 Ω |
Same-phase test repetition rate |
99.5% |
Power Supply | 220V±10%,50/60Hz (support customize) |
Net weight | less than 10KG |