Power Cable Insulation Testing 80kv Vlf Hipot Tester

Product Details
Customization: Available
After-sales Service: Lifetime Technical Support, Online Service
Warranty: 1 Year for Vlf Hipot Tester
Diamond Member Since 2007

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

Registered Capital
100800000 RMB
Plant Area
>2000 square meters
  • Power Cable Insulation Testing 80kv Vlf Hipot Tester
  • Power Cable Insulation Testing 80kv Vlf Hipot Tester
  • Power Cable Insulation Testing 80kv Vlf Hipot Tester
  • Power Cable Insulation Testing 80kv Vlf Hipot Tester
  • Power Cable Insulation Testing 80kv Vlf Hipot Tester
  • Power Cable Insulation Testing 80kv Vlf Hipot Tester
Find Similar Products
  • Overview
  • Product Description
  • Product Parameters
  • Product Functions
  • Various Versions
Overview

Basic Info.

Model NO.
VLF Hipot Tester
Display
Digital
Control
Manual Control
Weight
Controller: 4kg Booster: 25kg
Power Source
AC220V
Certificate
CE
Test Standard
IEC 60060
Output Voltage
30kv,40kv,50kv,60kv,80kv
Output Frequency
0.1Hz, 0.05Hz, 0.02Hz,0.01Hz
Stability of Frequency
Fluctuation < 0.5%
Measurement Error
< 3%Rdg+0.3%Fs
Voltage Wave Form Distortion
<5%
Power Supply Fuse Tube
25A
Application
Power Cable Insulation Withstand Test
Transport Package
Standard Wooden Case and Carton
Specification
as different requirements
Trademark
Vlf Hipot Tester
Origin
Chongqing, China (Mainland)
HS Code
9013809000
Production Capacity
300 Set/Sets Per Month

Product Description


Power Cable Insulation Testing 80kv VLF Hipot Tester 
 
Power Cable Insulation Testing 80kv Vlf Hipot Tester
Product Description

 

  • Power Cable Insulation Testing 80kv VLF Hipot Tester is designed and manufactured for electrical equipment very low frequency withstand voltage test.

  • Power Cable Very low frequency withstand voltage test is essentially an alternative of power frequency withstand voltage test. It is much smaller, lighter and portable than power frequency withstand voltage tester. It is proved home and abroad that 0.1Hz ultra-low frequency withstand voltage test can replace power frequency withstand voltage test.

  • It can be applied for 10kV, 35kV, 300MW thermal power machine, 10kV, 35kV power transformer and other electrical equipment.

Product Parameters

Power Cable Insulation Testing 80kv VLF Hipot Tester 

  • Max voltage output: refer to following table;

  • Output frequency: 0.1Hz, 0.05Hz, 0.02Hz,0.01Hz.

  • Measurement accuracy: 2.5%;

  • Positive and negative voltage peak errors < 2.5%RDG+0.3%FS;

  • Voltage wave form distortion:<3%;

  • Insulation resistance measurement error:<2.5%;

  • Leakage current measurement error:<2.5%;

  • Power supply:AC220V ± 10%, 50Hz/60Hz;

  • Environment temperature: 0~50°C;

  • Humidity:≤85%RH;

     

    Model Rated Voltage/current Load Carrying
    Capacity
    Product Structure and Weight
    VLF-30KV 30kV/20mA
    (Peak)
    0.1Hz,≤0.5µF~1.1µF Controller:4kg
    Booster: 25kg
    0.05Hz,≤0.5µF~2.2µF
    0.02Hz,≤0.5µF~5.5µF
    VLF-50KV 50kV/30mA
    (Peak)
    0.1Hz,≤0.5µF~1.1µF Controller:4kg
    Booster: 50kg
    0.05Hz,≤0.5µF~2.2µF
    0.02Hz,≤0.5µF~5.5µF
    VLF-60KV 60kV/30mA
    (Peak)
    0.1Hz,≤0.5µF Controller:4kg
    Booster Grade 1(30kV):25kg
    Booster Grade 2(30kV):25kg
    0.05Hz,≤0.5µF~1µF
    0.02Hz,≤0.5µF~2.5µF
    VLF-80KV 80kV/30mA
    (Peak)
    0.1Hz,≤0.5µF Controller:4kg
    Booster Grade 1(30kV):25kg
    Booster Grade 2(50kV):50kg
    0.05Hz,≤0.5µF~1µF
    0.02Hz,≤0.5µF~2.5µF

 

Product Functions

Power Cable Insulation Testing 80kv VLF Hipot Tester 

  • Data of current, voltage and wave form can be directly sampled at high voltage side, so the data is real and accurate;

  • Over-voltage protection: If the output exceeds the set limit of voltage, the instrument will shut-down to protect itself; the actuation time is less than 15ms;

  • Over-current protection: it is high-low voltage dual protection in the design, the accurate shut-down protection can be made according to the set value at high voltage side; If the current on low voltage side exceeds the rated current, the instrument will take shut-down protection, the actuation time are both less than 15ms;

  • A high voltage output protective resistor is provided in the voltage boost body in the design and this eliminates the need of additional protective resistor connected outside;

  • As a result of high and low voltage closed-loop negative feedback control circuit, the output without capacitive rise effect;

  • High-voltage control part adopts innovative light control HV switching unit, control is accurate, safe and reliable;

  • With color man-machine interface touch control plus controls modular software operating system, precise and intuitive;

  • Multi-purpose, can simultaneously measure tested objects capacitance, insulation resistance, leakage current, and AC withstand voltage test;
     

    Various Versions

    Power Cable Insulation Testing 80kv VLF Hipot Tester 

    Power Cable Insulation Testing 80kv Vlf Hipot Tester
    Power Cable Insulation Testing 80kv Vlf Hipot Tester

        VLF-30kV                                                                                                      VLF-40kV                                                      

    Power Cable Insulation Testing 80kv Vlf Hipot Tester
    Power Cable Insulation Testing 80kv Vlf Hipot Tester
    Power Cable Insulation Testing 80kv Vlf Hipot Tester

      VLF-50kV                                                                          VLF-60kV                                                                  VLF-80kV