Customization: | Available |
---|---|
After-sales Service: | All Life Technical Supports |
Warranty: | 1 Year |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
IMO Flame Spread Testing Equipment ISO 5658
Introduction:
IMO Flame Spread Testing Equipment ISO 5658 with Good Price is used to evaluate combustion characteristics of building materials and ship materials. It measures the spread rate of flame, the flame for ignition by distances, CFE (Critical Flux at Extinguishment), and total heat release.
IMO Flame Spread Testing Equipment ISO 5658 with Good Price method originated from ISO 5658-2 (Reaction to fire tests-Spread of flame- Part 2 Lateral spread on building products in vertical configuration) and measures combustion characteristics of the vertical specimen (155mmX800mm).
The specimen is exposed to a reasonable radiant heat field and is measured by a thermocouple for exhaust gas calibrated through the progress of combustion as a unit of mV. IMO records the spread rate of flame after this records ignition and extinguishment time of flame for each distance of specimens. The other test results are Heat for ignition (MJ/m2), Heat for sustained burning (MJ/m2), Critical flux at extinguishment (kW/m2), Average heat for sustained burning (MJ/m2), Total heat release (kW) and so on.
Standard:
1, ISO 5658-2: Reaction to fire tests -Spread of flame - Part 2 Lateral spread on building products in vertical configuration;
2, IMO Resolution A. 653(16): Recommendation on fire test procedures for flammability of bulkhead, ceiling, and deck finish materials'
3, ASTM E 1317: Standard test method for flammability of marine surface finishes.
Main Feature:
1, Rail for easily measuring heat flux of radiant panel at an interval of 50mm.
2, IMO Program to facilitate all calibrations and tests as well as to print out results by standards (IMO, ISO).
3, Radiant panel temperature controller: Equipment to prevent flame back toward the back side of the Radiant panel, check the internal temperature of the radiant panel, and automatically block gas sol. v/v in case of flame back-flow.
4, MFC (Mass Flow Controller) to easily measure the heat amount of methane gas in measuring critical heat flux.
5, Explosion-proof options of all control systems for safety in combustion in the radiant panel as well as Check-Valve and its
6, Gas shut-off valve (Solenoid Valve) to prevent back-flow in the gas line.
7, Camcorder to observe and save test conditions in a program during tests.
Specification:
Product Name | IMO Flame Spread Testing Equipment ISO 5658 |
Size | 1,650 (w) × 810 (D) × 1,985 (H) |
Power | 220 V AC, 60 Hz, 10 A |
Weight | 300 kg |
Exhaust | 0.01 m3/s |
Utilities | Propane Gas, Methane Gas, Acetylene Gas, Compressed Air |