12kv Anti-Interference Power Transformer Tan Delta Tester Insulation Power Factor Tester

After-sales Service: Lifetime Technical Support
Warranty: 1 Year for Transformer Tan Delta Tester
Type: Transformer Tan Delta Tester
Accuracy Grade: 1
Load Way: Electronic Load
Loading Method: Dynamic Load
Customization:
Diamond Member Since 2007

Suppliers with verified business licenses

Manufacturer/Factory, Trading Company

Basic Info.

Model NO.
GDGS
Display
Digital
Control
Manual Control
Weight
30kg
Power Source
AC220V
Product Name
Transformer Tan Delta Tester
Max Output Voltage
0-10kv
CVT Range
10-10000
Maximum Current
200mA
Capacity
2000va
Test Standard
IEC 60076
Transport Package
Plywood Case for Tan Delta Tester
Specification
30KG
Trademark
GOLD
Origin
Chongqing, China
HS Code
9030849000
Production Capacity
500 Sets/Month

Product Description

12KV Anti-Interference Power Transformer Tan Delta Tester Insulation Power Factor Tester
 
12kv Anti-Interference Power Transformer Tan Delta Tester Insulation Power Factor Tester

Introduction:

1) GDGS Automatic Transformer Power Factor Tester, Transformer Tan Delta Tester is a high-precision instrument, which can be applied to measure electrical loss tangent and capacitance of all kinds of high voltage electrical equipment in power plants, substations, laboratory, etc.
2) GDGS Automatic Transformer Power Factor Tester, Transformer Tan Delta Tester is an integrated structure, there is a dielectric loss test bridge, a variable frequency power supply, a step-up transformer and a SF6 high stability standard capacitor built-in;
3) It can also supply high voltage source for testing.
4) Frequency can be changed to 50Hz, 47.5Hz\52.5Hz,45Hz\55Hz, 60Hz, 57.5Hz\62.5Hz, 55Hz\65Hz; thus, it can avoid interference of power frequency;
12kv Anti-Interference Power Transformer Tan Delta Tester Insulation Power Factor Tester
 

Specifications:

No.

Item Name

GDGS Automatic Transformer Power Factor Tester

1

Use conditions

-15ºC∽40ºC

RH<80%

2

Anti-interference

Frequency conversion

3

Power

AC 220V±10%

 

4

High output

0.5KV∽10KV

Every 0.1kV

Precision

2%

Maximum current  

200mA

Capacity

2000VA

5

Self-excited power

AC 0V∽50V/15A

45HZ/55HZ 47.5HZ/52.5HZ

55HZ/65HZ 57.5HZ/62.5HZ

Automatic double frequency

6

Resolving power

tgδ: 0.001%

Cx: 0.001pF

7

Precision

△tgδ:±(Reading*1.0%+0.040%)

△C x :±(Reading*1.0%+1.00PF)

8

measuring range

tgδ

Unlimited

C x

15pF < Cx < 300nF

 

10KV

Cx < 60  nF

 

 5KV

Cx < 150 nF

 

 1KV

Cx < 300 nF

CVT test

Cx < 300 nF

9

CVT range

10∽10000

accuracy

0.1%

Resolving power

0.01

10

Exterior dimension

350(L)×270(W)×270(H)

11

Memory size

The 200 group supports U disk data storage

12

Weight

28 Kg


Product show
 
12kv Anti-Interference Power Transformer Tan Delta Tester Insulation Power Factor Tester
12kv Anti-Interference Power Transformer Tan Delta Tester Insulation Power Factor Tester


Customer Visit

12kv Anti-Interference Power Transformer Tan Delta Tester Insulation Power Factor Tester

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now