IEC76-1 and IEC60044 Portable TTR Handheld transformer turn ratio tester
Product introduction
- GDBC-901 Three Phase Transformer Turns Ratio TTR Tester is designed according IEC76-1 and IEC60044.
- GDBC-901 Three Phase Transformer Turns Ratio TTR Tester could be applied to test the turns ratio and group vector of single or three phase transformer.
- Also the connection group of transformer could be calculated with the ratio.
- All parameters are measured in one test for three phase transformer.
Product show
Application
- GDBC-901 Three Phase Transformer Turns Ratio TTR Tester is designed according IEC76-1 and IEC60044.
- The voltage ratio measurement for three or singe phase transformer
- The group vector measurement for three phase transformer.
- The polarity measurement for single phase transformer or CT/PT
- Voltage ratio error calculation
- Current transformer ratio measurement
- Excitation current measurement in ratio testing
- Reproduction the AC test voltage from power source to reduce the effects of bad power source
- Save the test results in the memory internal the tester
- Print the test results by micro printer
- Reverse connection detect unit to prevent the high voltage injected to operator
- Over current protection unit integrated in software and hardware
- Upload the test results to PC by RS232 and make word report by software
Specifications
1 |
Item Name |
GDBC-901 Single Phase and Three Phase Transformer Turns Ratio TTR Tester |
2 |
Ratio measurement range |
1-10000 |
3 |
Group measurement |
1-12 |
4 |
Phase measurement error |
1 degree |
5 |
Ratio measurement error |
1-2000 ± 0.2%RDG 2000-10000 ± 0.5%RDG |
6 |
Test voltage |
0~80V, frequency 50Hz |
7 |
Power supply |
AC220V ± 10%, 50Hz/60Hz |
8 |
Environment temperature |
0-50°C |
9 |
Humidity |
≤85%R |
10 |
Dimension |
58*45*36CM |
11 |
Weight |
22Kg |
Overseas Exhibition