Advanced Cable AC Vlf Hipot Tester High Voltage Tester
Overview:
Specifications:
* Max voltage output: refer to the following table
* Output frequency: 0.1Hz, 0.05Hz, 0.02Hz
* Measurement accuracy: 2.5%
* Positive and negative voltage peak errors: < 2.5%RDG+0.3%FS
* Voltage wave form distortion: <3%
* Insulation resistance measurement error: <2.5%
* Leakage current measurement error: <2.5%
* Power supply: AC220V ± 10%, 50Hz/60Hz
* Environment temperature: 0~50°C
* Humidity: ≤85%RH
Model |
Rated Voltage/current |
Load Carrying Capacity |
Power fuse wire |
30 |
30kV/20mA (Peak) |
0.1Hz,≤0.5µF~1.1µF |
5A |
0.05Hz,≤0.5µF~2.2µF |
|||
0.02Hz,≤0.5µF~5.5µF |
|||
50 |
50kV/30mA (Peak) |
0.1Hz,≤0.5µF~1.1µF |
7A |
0.05Hz,≤0.5µF~2.2µF |
|||
0.02Hz,≤0.5µF~5.5µF |
|||
60 |
60kV/30mA (Peak) |
0.1Hz,≤0.5µF |
9A |
0.05Hz,≤0.5µF~1µF |
|||
0.02Hz,≤0.5µF~2.5µF |
|||
80 |
80kV/30mA (Peak) |
0.1Hz,≤0.5µF |
12A |
0.05Hz,≤0.5µF~1µF |
|||
0.02Hz,≤0.5µF~2.5µF |