Customization: | Available |
---|---|
After-sales Service: | Lifetime Technical Support,Online Service |
Warranty: | 1 Year for Capacitance Power Factor Tester |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Our GDGS Transformer Tan Delta IPF Capacitance/Power Factor Test Set can automatically measure electrical loss tangent (Tgδ), capacitance and power factor of all kinds of high voltage electrical equipment on the spot of power plants, substations,laboratory, etc.
1 |
Use conditions |
-15ºC-40ºC |
RH<80% |
|
2 |
Anti-interference |
Frequency conversion |
||
3 |
Power |
AC 220V±10% |
||
4 |
High output |
0.5KV-10KV |
Every 0.1kV |
|
Precision |
2% |
|||
Maximum current |
200mA |
|||
Capacity |
2000VA |
|||
5 |
Self-excited power |
AC 0V∽50V/15A |
45HZ/55HZ 47.5HZ/52.5HZ 55HZ/65HZ 57.5HZ/62.5HZ Automatic double frequency |
|
6 |
Resolving power |
tgδ: 0.001% |
Cx: 0.001pF |
|
7 |
Precision |
△tgδ:±(Reading*1.0%+0.040%) |
||
△C x :±(Reading*1.0%+1.00PF) |
||||
8 |
Measuring range |
tgδ |
Unlimited |
|
C x |
15pF < Cx < 300nF |
|||
10KV |
Cx < 60 nF |
|||
5KV |
Cx < 150 nF |
|||
1KV |
Cx < 300 nF |
|||
CVT test |
Cx < 300 nF |
|||
9 |
CVT range |
10-10000 |
||
Accuracy |
0.1% |
|||
Resolving power |
0.01 |
|||
10 |
Exterior dimension |
350*270*270mm |
||
11 |
Memory size |
The 200 group supports U disk data storage |
||
12 |
Weight |
28 Kg |