• O-C-O Sequences Power System High Voltage Circuit Breaker Analyzer
  • O-C-O Sequences Power System High Voltage Circuit Breaker Analyzer
  • O-C-O Sequences Power System High Voltage Circuit Breaker Analyzer
  • O-C-O Sequences Power System High Voltage Circuit Breaker Analyzer
  • O-C-O Sequences Power System High Voltage Circuit Breaker Analyzer
  • O-C-O Sequences Power System High Voltage Circuit Breaker Analyzer

O-C-O Sequences Power System High Voltage Circuit Breaker Analyzer

After-sales Service: Lifetime Technical Support,Online Service
Warranty: 1 Year for Circuit Breaker Analyzer
Apparatus: Circuit Breaker Mechanical Characteristics Analyze
Application: High Voltage Circuit Breaker Analyzer
Function: IEC62271 12 Channels Gcb Circuit Breaker Analyzer
Device: IEC62271 Circuit Breaker Analyzer
Customization:
Diamond Member Since 2007

Suppliers with verified business licenses

Manufacturer/Factory, Trading Company
  • Overview
  • Product Description
  • Company Profile
Overview

Basic Info.

Model NO.
GDGK-307
Time Measurement
12 Channels
Operating Sequence
Co-T1-Co,O-T-Co-T1-Co,Co Rated Operating Sequence
Pre-Insertion Resistance Measurement
Range: 50~5000ohm; Error :<1%Rdg+2D
Dynamic Resistance Measurement
Test Current: 25~100A
Contact Resistance Measurement
Range:0-10mohm
Transport Package
Plywood Case
Specification
ISO Certificate
Trademark
GOLD
Origin
Chongqing of China
HS Code
9031809090
Production Capacity
200PCS/Month

Product Description

GDGK-307 O-C-O Sequences Power System Circuit Breaker Analyzer

O-C-O Sequences Power System High Voltage Circuit Breaker Analyzer
O-C-O Sequences Power System High Voltage Circuit Breaker Analyzer
O-C-O Sequences Power System High Voltage Circuit Breaker Analyzer
 
Product Description

The Circuit Breaker Analyzer is used for testing, analyzing and assessing power system circuit breakers, mechanical characteristics of load switches and isolated switches and other AC high voltage switches, contact resistance, Arcing contacts and vibration characteristics etc. The functions of Circuit Breaker Analyzer cover all testing items of high voltage circuit breaks.
 

 
Comparing with the traditional circuit breaker tester, this Circuit Breaker Analyzer has the following unique advantages:
 
1) The integrated vibration test function of Circuit Breaker Analyzer provides a new means of detection circuit breaker mechanical characteristics for users, compared to traditional time measurement and speed measurement, the vibration fingerprint detection is easier and more efficient.
2) The vibration fingerprint test results contain richer information of circuit breaker operation, for potential risk of failure or faulty breakers, it can locate the fault position quickly. 
3) The vibration tests do not need to change the original line connection, so the users can complete the charged detection of mechanical characteristics of circuit breaker.
4) Arcing contact analysis module allows users to automatically assess the degree of loss of inside Arc suppression contact of circuit breaker without disassembly.
5) Users can use Circuit Breaker Analyzer to complete the contact resistance tests, do not need to buy contact resistance tester separately.


Applications:
  • Measurement of closing time, opening time, time spread between poles, time spread between units of one pole, bounces etc.
  • Measurement of closing speed, opening speed and average speed.
  • Measurement of clearance between open contacts, over travel, overshoot travel and total travel.
  • Measurement of closing coil current time curve, opening coil current time curve and the maximum coil current.
  • Test travel time curve, speed time curve and acceleration time curve.
  • Measurement of pre-insertion resistance value and pre-insertion ion time.
  • Test contact resistance.
  • Measurement of dynamic resistance time curve and length for arcing contacts.
  • Vibration test, including vibration fingerprint curve acquisition, management, and vibration fingerprint curve automatic matching.
  • CO-t1-CO,O-t-CO-t1-CO,CO rated operating sequence verification test.
  • Drawing Envelopes for reference travel curve and compare travel curve with envelopes.
  • Mechanical travel curve automatic compare with saved travel curve.
  • Measurement of CO time (close-open time) and OC time (Opening-Closing time).
  • Graphite contact closing time, opening time, dynamic resistance curve measurement.
  • Zoom, editors, statistics and analysis for measurement curves.
  • 12.1-inch touch screen for control and data input
  • Built-in micro printer for test result printout.
  • Generate WORD format test report automatically (all reports and data can be exported through Flash disk).

Specifications:
  • 12 channels for time measurement
  •    3-channel supports both the time contact and resistance contact time
  •    6-channel isolated contacts for cascaded unit measurement of pole
  • Time measurement
  •    Range: 4000ms
  •    Error :< 0.1ms
  •    Resolution: 0.01ms
  • Travel measurement according to sensor:
  •    Linear resistance sensor: 
  •    Measurement range: 0~250mm; resolution: 0.01mm; error: <0.5mm
  •    Measurement range: 0~25mm; resolution: 0.01mm; error: <0.05mm
  •    Angle resistance sensor:
  •    Measurement range: 0~360°; resolution: 0.01°; error: <0.5°
  • Pre-insertion resistance measurement
  •    Range: 50~5000ohm; error :<1%RDG+2D
  • Dynamic resistance measurement
  •    Test current: 25~100A
  •    Measurement error :< 1%RDG+2D
  • Contact resistance measurement
  •    Range:0--10mohm
  •    Error <0.5%RDG+0.05%FS
  •    Range: 0-2mohm;
  •    Error: <0.5%RDG+2D
  • Speed measurement
  •    250mm linear resistance scale: 0~20m/s; error: <0.5%RDG+2D
  •    25mm linear resistance scale: 0~20m/s; error: <0.5%RDG+2D
  •    Angle sensor: 0~20m/s; error: <0.5%RDG+2D
  •    Acceleration sensor: 0~20m/s; error: <5%RDG+2D
  • Coil current measurement range: 0~20A; resolution: 0.001A; error: <0.01A
  • Vibration measurement range: 0~5000G; error: <3%
  • Internal DC power source: voltage: 12~265V; current:0~20A
  • Built-in 8G storage memory and 2 USB interface for data export and external keyboard or mouse connection
  • Power supply: AC220V±10%; 50Hz±10%
  • Working environment: temperature: -10~50°C; Humidity: <80%
O-C-O Sequences Power System High Voltage Circuit Breaker Analyzer
Company Profile

O-C-O Sequences Power System High Voltage Circuit Breaker AnalyzerO-C-O Sequences Power System High Voltage Circuit Breaker AnalyzerO-C-O Sequences Power System High Voltage Circuit Breaker AnalyzerO-C-O Sequences Power System High Voltage Circuit Breaker Analyzer

 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now

You Might Also Like

Diamond Member Since 2007

Suppliers with verified business licenses

Manufacturer/Factory, Trading Company
Registered Capital
100800000 RMB
Plant Area
>2000 square meters