Volt-ampere Characteristic Tester CT PT Transformer Analyzer
It is based on the well-received and applied fully automatic FA series transformer universal tester produced by our company. The use of high-performance DSP and ARM can complete the data acquisition of the variable frequency power supply control and test process, and the advanced manufacturing process ensures that the product performance is stable and reliable, with complete functions, high degree of automation and high efficiency. It is at the leading level in China and is a professional test equipment for transformer inspection in the power industry. All data analysis, storage and interface display are completed by the industrial computer system.
1. Excitation curve and parameters test
2. Turns ratio test
3. Ratio and phase error test
4. Polarity mark check
5. Winding resistance measurement
6. Secondary loop burden measurement
7. Error line curve test for protection CT
8. Transient CT parameters test
9. CT nameplate guess
10. Saturation hysteresis loop curve measurement
Tests for Potencial Transformer :
1. Turns ratio test
2. Ratio error and phase angle error test
3. Polarity test
4. Secondary burden test
5. Winding resistance test
1. CT nameplate check
2. CT parameters check in work burden
3. CT transient parameters analysis
4. CT ratio and phase error calibration
5. PT routine test
GDVA-405 CT PT Analyzer | ||
1 | Test standards | IEC60044-1/2/5/6, GB1208, GB61869, C57.13 |
2 | Power supply | AC220V±10%,50Hz/60Hz±10% |
3 | Power output | 0.1~125V (AC) |
4 | Current output | 0.001~5A(RMS) |
5 | Power output | 300VA |
6 | Max. knee voltage measurement | 45kv |
7 | Current measurement range | 0~10A (automatically change range in 0.1/0.4/2/10A) |
8 | Current measurement error | <±0.1%+0.01%FS |
9 | Voltage measurement range | 0~200 V (automatically change range in 1V/10V/70V/200V) |
10 | Voltage measurement error | < ±0.1%+0.01%FS |
11 | Turns ratio measurement range | 1~30000; 1~2000 error<0.05%; 2000~5000 error>0.1%; 5000~35000 error<0.2% |
12 | Phase measurement | error:±2min,resolution:0.01min |
13 | Coil resistance measurement | Range: 0~8kΩ(automatically change range in 2ohm /20ohm /80ohm/800ohm/8kohm) Error< 0.2%RDG+0.02%FS Maximum resolution: 0.1mΩ |
14 | Temperature measurement | -50~100 Celsius degree, error<3 Celsius degree |
15 | CT Secondary burden | Range 0-160ohm (automatically change range in 2ohm/ 20ohm/80ohm/160ohm) Error <0.2%RDG+0.02%FS Maximum resolution 0.001ohm |
16 | PT Secondary burden | Range 0-80kohm (automatically change range in 800ohm / 8kohm /80kohm) Error <0.2%RDG+0.02%FS Maximum resolution: 0.1ohm |
17 | PT ratio measurement | Range: 1~30000, 1~5000 error<0.2% 5000~30000 error<0.5% |
18 | Saved data groups | >1000 groups |
19 | Work condition | Temperature:-10ºC-50ºC, moist:≤90% |
20 | Size | 49*36*19cm |
21 | Net Weight | 15kg |
Name | Quantity | Description |
Host machine | 1 | |
3M mask cable | 2 | Test cable for power out and CT secondary connection |
10M mask cable | 1 | Test cable for CT primary connection |
Grounding cable | 1 | |
Big test pliers | 2 | One red and one black |
Test gasket | 4 | Two red and two black |
Test pin | 4 | Two red and two black |
Test pliers | 12 | Three red and nine black |
Short connection cable | 1 | Including six connection terminals |
3A fuse | 3 | |
Power cable | 1 | |
Accessories bag | 1 | |
Production disk | 1 | Include Analysis application and user manual |
User manual | 2 | |
Inspection report | 1 | |
Pass certificate | 1 |