After-sales Service: | Lifetime Technical Support |
---|---|
Warranty: | 1 Year for Transformer CT PT Parameter Analyzer |
Product Name: | CT PT Analyzer for Current Transformer |
Test Standards: | IEC60044-1/2/5/6 |
Power Supply: | 220V 50Hz |
Usage: | Transformer Tester |
Customization: |
---|
Suppliers with verified business licenses
Transformer CT PT Comprehensive Parameter Analyzer with IEC Standard
Overview:
The development of GDVA-405 Transformer CT PT Comprehensive Parameter Analyzer involved extensive customer input and in-depth theoretical research. They are the expert testing tools for transformer check in the power sector due to the use of high-performance DSP and ARM and sophisticated manufacturing technology, which guarantee a stable and dependable product performance, full-featured, high degree of automation, and high efficiency.
Main Test Items of GDVA-405:
Technical Parameters:
• IEC60044-1, IEC60044-6, GB1208, GB16847 and C57.13 test standards
• Power input: AC220V at 10%, 50%/60Hz at 10%
• Output power: 0.1-125V (AC)
• Output current: 0.001 to 5A (RMS)
• 300 VA power output
• 45kv is the maximum knee voltage measurement
• Current measurement:
Range:0~10A (automatically change range in 0.1/0.4/2/10A)
Error <±0.1%+0.01%
FS
• Voltage measurement:
Range:0~200 V (automatically change range in 1V/10V/70V/200V)
Error < ±0.1%+0.01%
FS
• Measurement of the 9 turns ratio:
Range:1~30000,
1~1000 error<0.05%
1000~2000 error<0.1%
• Phase measurement: resolution: 0.01 min, error: 2 min.
• Measuring coil resistance
Range:0 to 8k (automatically changing between 2 ohm, 20 ohm, 80 ohm, 800 ohm, and 8 k ohm).
Error 0.01%FS+0.1%RDG
0.1 m is the maximum resolution.
• Temperature measurement range: -50 to 100 Celsius, error range: 3 Celsius
• CT Secondary burden:
Range 0-160 ohm (automatically switches to 2 ohm, 20 ohm, 80 ohm, and 160 ohm)
2.2%RDG+0.02%FS error
The highest resolution is 0.001 ohm.
• PT Secondary burden:
Range 0-80 kohm (range automatically changes to 800 kohm, 8 kohm, and 80 kohm)
2.2%RDG+0.02%FS error
The highest resolution is 0.1 ohm.
• Groupings of saved data: over 1000 groups
• Work environment: Temperature: -10°C-50°C, 90% humidity
• Size: 485 mm x 356 mm x 183 mm
• Pounds: 15 kg
• 2000~30000 error<0.2%
More Details of Transformer CT PT Comprehensive Parameter Analyzer:
Suppliers with verified business licenses