Transformer vacuum drying equipment Transformer Maintenance apparatus Dry Air Generator
It is mainly used for vacuum drying and vacuum oil -injecting for high voltage electrical transformer as 220kV, 500kV, ±800kV, 1000kV. Strong vacuum pumps make working vacuum degree to 10 Pa and limit vacuum degree to 1Pa
Item | Parameter | Unit | GF-50 | GF-100 | GF-150 | GF-200 |
---|---|---|---|---|---|---|
Technical Parameter |
Flow Rate | M3/H | 50 | 100 | 150 | 200 |
Working Pressure | Mpa | 0.6-0.8 | ||||
Pressure Loss | ≤0.05Mpa | |||||
Pressure Drop | Mpa | 0.05 | ||||
Noise | Db(A) | ≤70 | ||||
Working Power | kW | 380V, 50Hz, 3 Phase 4 Wire | ||||
Total Power | kW | 12 | 19 | 22 | 26 | |
Length | cm | 215 | 215 | 230 | 230 | |
Width | cm | 155 | 155 | 165 | 165 | |
Height | cm | 230 | 230 | 230 | 230 | |
Weight | kg | 900 | 980 | 1030 | 1050 | |
After Treatment Index |
Discharge Pressure | Mpa | 0.02-0.03 | |||
Dew Point | °C | -50°C~-70°C | ||||
Particle | μm | 0.01 | ||||
Oil Content In Air Outlet | ppm | 0.01 |