• Gdbc-901 Automatic Three Phase Transformer Turns Ratio Tester TTR Meter
  • Gdbc-901 Automatic Three Phase Transformer Turns Ratio Tester TTR Meter
  • Gdbc-901 Automatic Three Phase Transformer Turns Ratio Tester TTR Meter
  • Gdbc-901 Automatic Three Phase Transformer Turns Ratio Tester TTR Meter
  • Gdbc-901 Automatic Three Phase Transformer Turns Ratio Tester TTR Meter

Gdbc-901 Automatic Three Phase Transformer Turns Ratio Tester TTR Meter

After-sales Service: Lifetime Technical Support, Online Service
Warranty: 1 Year for Transformer TTR Meter
Power Supply: 220V 50Hz
Application Field: Electrical Industry
Standard: IEC76-1, IEC60044
Group Measurement: 1-12
Customization:
Diamond Member Since 2007

Suppliers with verified business licenses

Manufacturer/Factory, Trading Company

Basic Info.

Model NO.
GDBC-901
Phase Measurement Error
91 Degree
Environment Temperature
0-50°c
Test Voltage
0~80V, Frequency 50Hz
Humidity
≤85%Rh
Transport Package
Standard Wooden Case
Specification
ISO
Trademark
GOLD
Origin
Chongqing
HS Code
9031809090
Production Capacity
500PCS/Month

Product Description

GDBC-901 Three Phase Transformer Turns Ratio Tester TTR Meter
1) GDBC-901 Three Phase Transformer Turns Ratio TTR Tester is designed according IEC76-1 and IEC60044.
2) GDBC-901 Three Phase Transformer Turns Ratio TTR Tester could be applied to test the turns ratio and group vector of single or three phase transformer.
3) Also the connection group of transformer could be calculated with the ratio.
4) All parameters are measured in one test for three phase transformer.
Gdbc-901 Automatic Three Phase Transformer Turns Ratio Tester TTR Meter

 

Main Functions:

  • The voltage ratio measurement for three or singe phase transformer 

  • The group vector measurement for three phase transformer.

  • The polarity measurement for single phase transformer or CT/PT

  • Voltage ratio error calculation

  • Current transformer ratio measurement

  • Excitation current measurement in ratio testing

  • Reproduction the AC test voltage from power source to reduce the effects of bad power source

  • Save the test results in the memory internal the tester

  • Print the test results by micro printer

  • Reverse connection detect unit to prevent the high voltage injected to operator

  • Over current protection unit integrated in software and hardware

  • Upload the test results to PC by RS232 and make word report by software

 

Specifications:

1 Item Name GDBC-901 Single Phase and Three Phase Transformer Turns Ratio TTR Tester
2 Ratio measurement range 1-10000
3 Group measurement 1-12
4 Phase measurement error 1 degree
5 Ratio measurement error 1-2000 ± 0.2%RDG   2000-10000  ± 0.5%RDG
6 Test voltage 0~80V, frequency 50Hz
7 Power supply AC220V ± 10%, 50Hz/60Hz
8 Environment temperature 0-50°C
9 Humidity ≤85%R
10 Dimension 58*45*36CM
11 Weight 22Kg
 

Benefits:

  • The test power supply is generated by the internal power amplifier of the tester, and the waveform distortion rate is less than 0.5% and is not affected by the quality of power supply.

  • Automatic voltage regulation, with automatic protection functions such as transformer reverse connection, over-current, etc., to avoid damage to the instrument due to incorrect operation.

  • It can be used for power transformer, CT and PT ratio detection.

  • Convenient standard transformation ratio setting template, don't need to manually calculate the standard transformation ratio value.

  • GDBC-901 is very light, only 20KG. It's easy to carry. It's suitable for field test.

 


Product Show:
Gdbc-901 Automatic Three Phase Transformer Turns Ratio Tester TTR Meter
Gdbc-901 Automatic Three Phase Transformer Turns Ratio Tester TTR Meter


Accessories:
Gdbc-901 Automatic Three Phase Transformer Turns Ratio Tester TTR Meter


Gdbc-901 Automatic Three Phase Transformer Turns Ratio Tester TTR Meter
Gdbc-901 Automatic Three Phase Transformer Turns Ratio Tester TTR MeterGdbc-901 Automatic Three Phase Transformer Turns Ratio Tester TTR MeterGdbc-901 Automatic Three Phase Transformer Turns Ratio Tester TTR MeterGdbc-901 Automatic Three Phase Transformer Turns Ratio Tester TTR Meter

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now

You Might Also Like

Diamond Member Since 2007

Suppliers with verified business licenses

Manufacturer/Factory, Trading Company
Registered Capital
100800000 RMB
Plant Area
>2000 square meters