Hv Tan Delta Integrated Test System Power Factor Test Sets for Transformer and Generator

Product Details
Customization: Available
After-sales Service: Lifetime Technical Support,Online Service
Warranty: 1 Year
Diamond Member Since 2007

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

Registered Capital
100800000 RMB
Plant Area
>2000 square meters
  • Hv Tan Delta Integrated Test System Power Factor Test Sets for Transformer and Generator
  • Hv Tan Delta Integrated Test System Power Factor Test Sets for Transformer and Generator
  • Hv Tan Delta Integrated Test System Power Factor Test Sets for Transformer and Generator
  • Hv Tan Delta Integrated Test System Power Factor Test Sets for Transformer and Generator
  • Hv Tan Delta Integrated Test System Power Factor Test Sets for Transformer and Generator
  • Hv Tan Delta Integrated Test System Power Factor Test Sets for Transformer and Generator
Find Similar Products

Basic Info.

Model NO.
GDGS
Anti-Interference
Frequency Conversion
Power
AC 220V±10%
High Output
10kv(Can Customize 12kv)
Maximum Current
200mA
Capacity
2000va
Self-Excited Power
AC 0V∽50V/15A
CVT Range
10∽10000
Accuracy
0.1%
Resolving Power
0.01
Weight
About 35kg
Transport Package
Plywood Case
Specification
35kg
Trademark
GOLD
Origin
Chongqing, China
HS Code
9030849000
Production Capacity
200piece/Month

Product Description

HV Tan Delta Integrated Test System Power Factor Test Sets for Transformer and Generator

Hv Tan Delta Integrated Test System Power Factor Test Sets for Transformer and Generator

 

Introduction:

  • The GDGS dielectric loss tester has extremely high test stability. The dielectric loss value and the capacitance value are stable. The sampling avoids the test voltage of the power frequency and performs digital filtering on the power frequency voltage. The test data is stable and reliable.
  • GDGS dielectric loss tester breaks through the traditional bridge measurement method, adopts frequency conversion power supply technology, uses single chip microcomputer and modern electronic technology to carry out automatic frequency conversion, analog/digital conversion and data calculation; achieves strong anti-interference ability, fast test speed and high precision, fully automatic digital, easy to operate; power supply uses high-power switching power supply, output 45Hz and 55Hz pure sine wave, automatic pressure, can provide up to 10kV voltage; automatic filter 50Hz interference, suitable for substation and other electromagnetic interference Field test.
  • The inter-frequency dielectric loss tester can effectively find the overall moisture deterioration and deterioration of electrical equipment insulation, as well as local defects, etc., used for transformer windings, transformer bushings, transformer dielectric loss test, current transformer dielectric loss, current Transformer final screen dielectric loss test, voltage transformer dielectric loss, capacitive voltage transformer dielectric loss, circuit breaker, high voltage switch dielectric loss test, shunt capacitor, coupling capacitor dielectric loss test; in electrical engineering, electrical equipment installation, handover and Widely used in preventive trials.



Specifications:

No.

Item Name

GDGS Automatic Transformer Power Factor Tester

1

Use conditions

-15ºC∽40ºC

RH<80%

2

Anti-interference

Frequency conversion

3

Power

AC 220V±10%

Allowable generator

4

High output

0.5KV∽10KV

Every 0.1kV

Precision

2%

Maximum current  

200mA

Capacity

2000VA

5

Self-excited power

AC 0V∽50V/15A

45HZ/55HZ 47.5HZ/52.5HZ

55HZ/65HZ 57.5HZ/62.5HZ

Automatic double frequency

6

Resolving power

tgδ: 0.001%

Cx: 0.001pF

7

Precision

△tgδ:±(Reading*1.0%+0.040%)

△C x :±(Reading*1.0%+1.00PF)

8

measuring range

tgδ

Unlimited

C x

15pF < Cx < 300nF

 

10KV

Cx < 60  nF

 

 5KV

Cx < 150 nF

 

 1KV

Cx < 300 nF

CVT test

Cx < 300 nF

9

CVT range

10∽10000

accuracy

0.1%

Resolving power

0.01

10

Exterior dimension

350(L)×270(W)×270(H)

11

Memory size

The 200 group supports U disk data storage

12

Weight

35 Kg(With package)


Functions:

1) The instrument uses a complex current method to measure capacitance, dielectric loss and other parameters. The test results are highly accurate and easy to automate measurements.

2) The instrument adopts frequency conversion technology to eliminate on-site 50Hz power frequency interference, and can measure reliable data even in the environment of strong electromagnetic interference.

3) The instrument adopts large-screen liquid crystal display, and the test process is intuitive and easy to operate through the Chinese character menu prompt.

4) The instrument is easy to operate, and the measurement process is controlled by the microprocessor. As long as the appropriate measurement method is selected, the measurement of the data can be automatically performed under the control of the microprocessor.

5) Integrated model with standard capacitor and high voltage power supply for on-site testing and field wiring reduction.

6) The instrument has high measurement accuracy and can meet the oil dielectric loss measurement requirements. Therefore, only the standard oil cup and the special test line can be used to measure the oil dielectric loss.

7) Set CVT test function, can realize CVT self-excitation test, no need external accessories, only in one test , C1, C2 capacitance and dielectric loss are all measured.

8) Reverse wiring test adopts ivddv technology, which eliminates the instability of the reverse wiring data.

9) With reverse wiring low-voltage shielding function, in the case of 220kVCVT busbar grounding, C11 can be used for 10kV reverse wiring dielectric loss measurement without disconnection

10) With the function of measuring high voltage dielectric loss, it can conduct dielectric loss test with voltage exceeding 10kV using high voltage transformer or series resonance.

11) Grounding protection function, when the instrument is not grounded or the grounding is poor, the instrument does not enter the normal program and does not output high voltage. Overcurrent protection function, the instrument is not damaged when the sample is shorted or broken down.

12) Electrical protection function, when the instrument operator accidentally touches the electric power, the instrument will cut off the high voltage immediately to ensure the safety of the test personnel.


Hv Tan Delta Integrated Test System Power Factor Test Sets for Transformer and Generator
Hv Tan Delta Integrated Test System Power Factor Test Sets for Transformer and GeneratorHv Tan Delta Integrated Test System Power Factor Test Sets for Transformer and GeneratorHv Tan Delta Integrated Test System Power Factor Test Sets for Transformer and GeneratorHv Tan Delta Integrated Test System Power Factor Test Sets for Transformer and GeneratorHv Tan Delta Integrated Test System Power Factor Test Sets for Transformer and Generator


 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now
Contact Supplier