Cone Calorimeter Fire Testing Equipment ISO 5660 Flammability Analyze
Introduction:
Cone Calorimeter Fire Testing Equipment ISO 5660 Flammability Analyzer measures heat release rate(H.R.R), smoke release, ignition time, oxygen consumption, carbon monoxide, and carbon dioxide generation and mass loss rate when the specimen is exposed to the resource of the conical heater.
The name of the Cone Calorimeter is derived from the conical heater used by Dr. Vytenis Babrauskas to inspect test specimens (100mm*100mm) with flux up to 100kW/m2 for the bench-scale oxygen depletion of his development.
Cone Calorimeter Fire Testing Equipment ISO 5660 Flammability Analyzer is based on the theory that pure combustion calories are proportional to a necessary amount of oxygen for combustion and 13.1 MJ/kg is generated whenever oxygen 1kg is consumed. Heat emission, ignition time, oxygen consumption, CO and CO2 generation, and flow of ignited gases as generated from test materials are measured.
Cone Calorimeter Fire Testing Equipment ISO 5660 Flammability Analyzer is made for easily controlling the whole parts with the DAQ (Data Acquisition) Program in a laboratory. 19" touch screen helps to test automatically and reduce installation space.
Additionally, the Conical Heater 5-Step Heat Flux Controller (optional part for R&D purposes) helps to measure combustion characteristics of specimens by temperature change and temperature rising time after setting up the virtual temperature of real fire conditions. This option helps to measure various results similar to the real fire environment. Users can set up the user's temperature, rising speed, and lasting time after rising with the 5 Step Heat Flux Controller and use it easily.
Application:
- Building Materials
- Rail
- IMO
- Wire & Cable
- Other
Standard:
- ISO 5660: Reaction to fire tests - Heat release, smoke production, and mass loss rate;
- ASTM E 1354: Standard Test Method for Heat and Visible Smoke Release Rates for Materials and Products Using an Oxygen Consumption Calorimeter;
- BS 476 Pt.15: Fire tests on building materials and structures - Method for measuring the rate of heat release of products;
Detailed Image:
Features:
1, Integrated body and 19" analysis rack.
2, 17" touch screen panel type PC for the whole control and automatic testing.
3, Automatic Spark Igniter to facilitate measurement of ignition time.
4, Auto Split Shutter automatically opened to transmit radiation to the sample.
5, Absorber-type glass protection door to facilitate sample observation during testing and opening and closing.
6, UK Servomex's Gas Analyzer to exactly measure O2, CO, and CO2 concentrations up to 0.02%.
7, Port, heated filter, and heated line to measure toxic gases.
8, MFC(Mass Flow Controller) is used for all gas flows, improving accuracy and automatically controlling flux.
9, Portable water cooling system without the need for waterworks and plumbing when using the Heat Flux-meter (for ISO 5660).
10, UK RS' Load Cell with improved accuracy to measure mass loss rate.
11, CC 2006 DAQ(Data Acquisition) Program controllable with the touch screen panel PC.
Test Result:
Heat Flux, Unit: kW/m2
Exhaust duct flow rate, Unit: l/s
C factor, Unit:1/kg*m*K
Ignition time and Extinguishment time, Unit: s
Total oxygen consumption, Unit: g
Total Smoke Release, Unit: m/m2
Mass loss and Mass loss rate, Unit: g, g/s
Heat release rate, Unit: MJ/kg, kw/m2
Effective heat of combustion, Unit: MJ/kg
Carbon monoxide yield, Unit: kg/kg
Carbon dioxide yield, Unit: kg/kg
Specification:
Product name |
Cone Calorimeter Fire Testing Equipment ISO 5660 Flammability Analyzer |
Size |
1,800mm(W) * 900mm(D) *2,650mm(H) |
Weight |
about 450 kg |
Manual |
Supplied |
Exhaust |
50 l/s |
Utilities |
Compressed Air, Methane, Nitrogen, CO/CO2 Mixing Gas, Dust Collector |
Power |
110V AC 60Hz / 230V AC 50Hz, 15A |