Transformer tester calibrator | Verification device for volt ampere characteristic comprehensive tester
The current transformer calibration device is primarily designed for verifying the performance indicators of the current transformer comprehensive characteristic tester, including its volt-ampere characteristic testing, DC resistance measurement, and ratio testing.
The device incorporates four different types of standard current transformers to simulate the actual volt-ampere characteristic curves of current transformers and to evaluate their turns ratio measurements. During the inspection of the current transformer comprehensive characteristic tester, the calibration device's CT serves as the test specimen. Upon completion of the test, the actual measurement data obtained from the tester are compared with the corresponding standard curve of the CT to determine the test results.
1. Install 9 sets of CT standard coils with built-in standard protection, corresponding to a saturation voltage range of 0-5000V for the volt ampere characteristic curve, and a maximum detectable inflection point voltage greater than 4500V.
1) The accuracy of inflection point identification is greater than 1%
2) Voltage current identification error of volt ampere characteristic curve shall not exceed 0.5% reading+2D
2. The measurement range is 0-2000, and the ratio error identification error does not exceed 0.05%
3. The identification error of the coil remanence coefficient Kr shall not exceed 2%
According to the comparison program, the test data to be tested can be automatically compared with the curve of the standard CT
5. The coil winding provides 10KV insulation for the casing
6. The number of volt ampere characteristic points calibrated for each winding shall not be less than 100
7. The working cycle is that the time interval between two tests of the same coil winding should be more than 3 minutes
8. Working temperature 0-50 degrees, environmental humidity less than 85%
1.Calibration of the current method transformer characteristic tester
Ratio 2000-1/1 calibration
2.Calibration of the voltage-type transformer characteristic tester
Ratio 2000-1/1 calibration
3.Calibration of the volt-ampere characteristic test
4.Remanent Magnetism Coefficient Calibration
Electric Power Science Research Institute:
Used for regular calibration and verification of all transformer comprehensive testers (CT/PT analyzers) in subordinate units to ensure accurate power measurement data.
Manufacturer of Transformer Tester:
Conduct factory inspection and precision debugging before the product leaves the factory.
Third party testing agency:
Provide inspection services for self owned power plants of power construction units, chemical plants, or large steel mills.
Large enterprises and laboratories:
To conduct internal annual self calibration, saving inspection costs and time.