Introduction:
The instrument utilizes a sophisticated current method to measure capacitance, dielectric loss, and other parameters, providing precise and easily automated measurements.
It adopts frequency conversion technology to eliminate 50Hz power frequency interference on-site, ensuring reliable data measurement in environments with strong electromagnetic interference.
Featuring a large-screen LCD display, the instrument offers an intuitive test process that is easy to operate through Chinese character menu prompts.
Operation is straightforward, with the measurement process controlled by a microprocessor, allowing for automatic data measurement under microprocessor control.
It is an integrated model with a standard capacitor and high-voltage power supply for on-site testing, reducing the need for field wiring.
With high measurement accuracy, the instrument meets oil dielectric loss measurement requirements, requiring only a standard oil cup and special test line for oil dielectric loss measurement.
It includes a CVT test function, enabling CVT self-excitation testing without external accessories. In a single test, C1, C2 capacitance, and dielectric loss are all measured.
Reverse wiring tests employ ivddv technology, eliminating instability in reverse wiring data.
Featuring a grounding protection function, the instrument prevents operation without proper grounding. It also has overcurrent protection, safeguarding the instrument from damage if the sample is shorted or breaks down.
An electrical protection function immediately cuts off the high voltage if the instrument operator accidentally touches an electric power source, ensuring the safety of testing personnel.
Specifications:
No. | Item Name | Transformer Tan Delta Tester,Capacitance Dielectric Loss and Dissipation Factor Tester | |||
1 | Use conditions | -15ºC∽40ºC | RH<80% | ||
2 | Anti-interference | Frequency conversion | |||
3 | Power | AC 220V±10% | Allowable generator | ||
4 | High output | 0.5KV∽10KV | Every 0.1kV | ||
Precision | 2% | ||||
Maximum current | 200mA | ||||
Capacity | 2000VA | ||||
5 | Self-excited power | AC 0V∽50V/15A | 45HZ/55HZ 47.5HZ/52.5HZ 55HZ/65HZ 57.5HZ/62.5HZ Automatic double frequency |
||
6 | Resolving power | tgδ: 0.001% | Cx: 0.001pF | ||
7 | Precision | △tgδ:±(Reading*1.0%+0.040%) | |||
△C x :±(Reading*1.0%+1.00PF) | |||||
8 | measuring range | tgδ | Unlimited | ||
C x | 15pF < Cx < 300nF | ||||
10KV | Cx < 60 nF | ||||
5KV | Cx < 150 nF | ||||
1KV | Cx < 300 nF | ||||
9 | CVT range | 10∽10000 | |||
accuracy | 0.1% | ||||
Resolving power | 0.01 | ||||
10 | Exterior dimension | 350(L)×270(W)×270(H) | |||
11 | Memory size | The 200 group supports U disk data storage | |||
12 | Weight | 35 Kg(With package) |