Three-Phase Relay Tester Secondary Current Injection Test Set
Features:
- Satisfies all requirements for field tests. Relay Current Protection Overcurrent Relay Tester features a conventional six-phase output of 125 volts per phase, 30 amps per phase, and a maximum current capacity of 180 amps for six paralleled phases. microcomputer that uses a digital signal processor. Test contemporary microcomputer replays in addition to classic relays and protectors, particularly those designed for transformer differential protection and transfer equipment.
- The relay computer test device's technical condition standard DL/T624-1997 is completely complied with by all technical indications.
- Traditional Windows XP operating system, pleasant man-machine interface, quick and easy to use; High-performance embedded industrial control computer and 8.4 inch 8.4 inch resolution of 800*600 TFT true color display that delivers rich visual information, includes the present working status and all types of assistance information.
- The Windows XP operating system has a restoration feature that helps users prevent crashes brought on by unauthorized shutdowns, malfunctions, etc.
- With the help of the optical mouse and ultra-thin industrial keyboard, you may do a number of tasks just as on a regular PC.
- The primary control board has a DSP + FPGA design, a 16 bit DAC output, and creates high-density sine waves with 2000 points per circle for the fundamental wave, considerably enhancing the test instrument's wave quality and accuracy.
- Utilizing a high-end linear amplifier. In order to guarantee the accuracy of a low current and the stability of the high current.
- Without the need for an adaptor cable, USB is simple to utilize.
- Relay Current Protection Overcurrent Relay Tester is compatible with laptop computers (optional).
- There is no need to re-learn how to operate industrial machinery or laptop computers because they both use the same software.
- People can do a remote synchronization swap test for the two testers using the device's optional built-in GPS synchronization card, which connects to a PC via RS232.
- Relays or other safety devices that need DC power can be powered by a separate DC auxiliary voltage source with output voltages of 110V(1A) and 220V(0.6A).
- The accuracy is much more stable because to the software's self-calibrating feature, which prevents the need to calibrate accuracy by adjusting relays after opening the case.
Parameters:
1. AC current source (3 * 40a)
Single phase current output (RMS) |
0-40A / phase, accuracy: 0.2% ±5mA |
Three phase parallel output (RMS) |
0-120A / three phase in phase parallel output |
Allowable working value of phase current for a long time (effective value) |
10A |
Maximum output power per phase |
400VA |
Maximum output power of three phase parallel current |
1000VA |
Maximum output allowable working time of triple parallel current |
10s |
Frequency range |
0-1000Hz, accuracy 0.01Hz |
Harmonic number |
2-20second |
Phase |
0-360, accuracy 0.1 degree |
2. DC current source
DC current output |
- ±10A / phase,
Accuracy 0.2%±5mA |
3. AC voltage source
Single phase voltage output (RMS) |
0-125V / phase, Accuracy 0.2%±5mv |
Line voltage output (RMS) |
0-250V |
Phase voltage / line voltage output power |
75VA/100VA |
Frequency range |
0-1000Hz, accuracy 0.001Hz |
Harmonic number |
2-20second |
Phase |
0-360Degree, Accuracy 0.1 degree |
4. DC voltage source
Single phase voltage output amplitude |
0-±150V,
Accuracy 0.2%±5mv |
Output amplitude of line voltage |
0-±300V |
Phase voltage / Line voltage output power |
90VA/180VA |
5. Switching value terminal
Switch input terminal |
8yes |
Air contact |
1-20 mA, 24 V, internal active output of the device |
Potential reversal |
Passive contact: low resistance short circuit signal Active contact: 0-250V DC |
Switch output terminal |
4yes, no contact, breaking capacity: 110V / 2a, 220V / 1a |
6. Others
Time frame |
1ms-9999s, measuring accuracy: 1ms |
Volume and weight of portable series single machine |
Volume 338*168*305mm, about 12kg |
Power Supply |
AC220V±10%,50Hz,10A |
Display of Three-Phase Relay Tester Secondary Current Injection Test Set:
Other models
Single phase Six phase