High Accuracy Transformer Test Equipment CT PT Analyzer Voltage Transformer Tester
Characteristics
The CT PT Analyzer is extensively utilized in the installation, testing, and maintenance of transformers in power transmission and distribution systems, power plants, and related industries. It can perform various functions, such as testing turn ratio, phase angle analysis, excitation current measurement, polarity check, burden measurement, coil resistance testing, short-circuit impedance measurement, and saturation analysis.
Testing and resultsTest standard | IEC60044-1/2/5/6 IEEE C57.13 |
Input power voltage | AC220V±10%,50Hz/60Hz±10% |
Output voltage and current | 0.1-180V(AC) 0.001-5A(RMS) |
Output power | 500VA |
Max. inflection voltage | 45KV |
Current measurement | Range:0-10A(Automatic measuring range 0.1/0.4/2/10A) Error:<±0.1%+0.01%FS |
Voltage measurement | Range:0~200 V (Automatic measuring range 1/10/70/200V) Error:< ±0.1%+0.01%FS |
Turns ratio measurement | Range:1-35000 Error:<0.05% (1-5000) <0.1% (5000-35000) |
Ratio measurement | Typical error <0.02% Guaranteed error <0.1% |
Angle difference measurement | Accuracy: ±2min, Resolution: 0.01min |
Secondary winding resistance measurement range | Range:0-8000Ω(Auto range 2/20/80/800/8000Ω) Error< 0.2%RDG+0.02%FS Maximum resolution: 0.1mΩ |
Temperature measurement | -50-100 degrees Error <3 degrees |
CT secondary load measurement | Range:0-160ohm(2/20/80/160ohm) Error:0.2% RDG + 0.02% FS Maximum resolution:0.001ohm |
PT secondary load measurement | Range:0-80kohm(800ohm/8kohm/80kohm) Error:0.2%RDG+0.02%FS Maximum resolution:0.1ohm |
PT Turns ratio measurement | Range: 1-30000 Error:<0.1% (1-10000 ) <0.2%(10000-30000) |
Electromagnetic PT ratio measurement | Typical error <0.05% Guaranteed error <0.1% |
Electromagnetic PT angular difference measurement | Error <3 points |
Number of data storage groups | More than 1000 groups |
Working conditions | Temperature: -10 ºC -50 ºC Humidity: ≤ 90% |
Size | 490mm×360mm×190mm |
Weight | 15Kg |