Customization: | Available |
---|---|
After-sales Service: | Lifetime Technical Support |
Warranty: | 1 Year for Transformer CT PT Vt Analyzer |
Still deciding? Get samples of US$ 6800/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Main Features
• Measure CT and PT ratios at high voltage levels
• Accurately measure phase shift and ratio error
• Automatic ratio and polarity testing for quick and easy testing
• Measure load and resistance of secondary windings
• Analyze transient performance response under abnormal conditions
• Large LCD screen for clear display of test results and parameters
• Compact, rugged design for substations and switchyards
Specifications
Test standards | IEC60044-1, IEC60044-6, IEC60044-2, IEC60044-5, IEC61869,IEEE Std C57.13-2016 | |
Power supply |
AC220V±10%, 50/60Hz±10% (Support customize to AC110V,120V,127V) |
|
Voltage output | 0.1-180V (AC) | |
Current output | 0.001-5A(RMS) | |
Power output | 500VA | |
Max. knee voltage measurement | 60KV | |
Current measurement |
Range | 0-10A (automatically change range in 0.1/0.4/2/10A) |
Error | <±0.1%+0.01%FS |
Voltage measurement |
Range | 0-200V (automatically change range in 1V/10V/70V/200V) | |
Error | < ±0.1%+0.01%FS | ||
Turns ratio measurement Range |
1~35000 1~2000, error<0.05% 2000~5000,error<0.1% 5000~35000,error<0.2% |
||
Phase measurement | error | ±2min | |
resolution | 0.01min | ||
Winding resistance measurement |
Range | 0-8kΩ (automatically change range in2ohm/20ohm/80ohm/800ohm/8kohm) | |
Error | < 0.2%RDG+0.02%FS | ||
Maximum resolution : 0.1mΩ | |||
Temperature measurement | -50-100 Celsius degree; error<3 Celsius degree | ||
CT Secondary burden | Range | 0-160ohm (automatically change range in 2ohm/20ohm/80ohm/160ohm) | |
Error | <0.2%RDG+0.02%FS | ||
Maximum resolution : 0.001ohm | |||
PT Secondary burden |
Range | 0-80kohm (automatically change range in 800ohm/8kohm/80kohm) | |
Error | <0.2%RDG+0.02%FS | ||
Maximum resolution : 0.1ohm | |||
PT ratio measurement |
Range |
1-35000, 1-10000 error<0.1%, 10000-35000 error<0.2% |
|
PT ratio error measurement :Typical error<0.05%, Maximum Error<0.1% | |||
PT phase angle measurement maximum error < 3min | |||
Memory capacity | >1000 groups test results | ||
Working condition temperature | -10ºC-50ºC; moist ≤90% |
Main Test Function
CT (protection, measurement) | PT |
Volt-ampere characteristic (excitation characteristic) curve | Volt-ampere characteristic (excitation characteristic) curve |
Automatically give the inflection point value | Automatically give the inflection point value |
Automatically give 5% and 10% error curves | Transformation ratio measurement |
Transformation ratio measurement | Polarity judgment |
Polarity judgment | Ratio measurement |
One flow test | Angle difference measurement |
Ratio measurement | AC withstand voltage test |
Angle difference measurement | Secondary load test |
AC withstand voltage test | Secondary winding test |
Secondary load test | Iron core demagnetization |
Secondary winding test | |
Iron core demagnetization |
Packing List
Name | Quantity | Description |
Host machine | 1 | |
3M mask cable | 2 | Test cable for power out and CT secondary connection |
10M mask cable | 1 | Test cable for CT primary connection |
Grounding cable | 1 | |
Big test pliers | 2 | One red and one black |
Test gasket | 4 | Two red and two black |
Test pin | 4 | Two red and two black |
Test pliers | 12 | Three red and nine black |
Short connection cable | 1 | Including six connection terminals |
3A fuse | 3 | |
Power cable | 1 | |
Accessories bag | 1 | |
Production disk | 1 | Include Analysis application and user manual |
User manual | 2 | |
Inspection report | 1 | |
Pass certificate | 1 |