Current Transformer Tester CT PT Analyzer

Product Details
Customization: Available
After-sales Service: Lifetime Technical Support
Warranty: 1 Year for Transformer CT PT Vt Analyzer
Still deciding? Get samples of US$ 6800/Piece
Request Sample
Diamond Member Since 2007

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

Registered Capital
100800000 RMB
Plant Area
>2000 square meters
  • Current Transformer Tester CT PT Analyzer
  • Current Transformer Tester CT PT Analyzer
  • Current Transformer Tester CT PT Analyzer
  • Current Transformer Tester CT PT Analyzer
  • Current Transformer Tester CT PT Analyzer
  • Current Transformer Tester CT PT Analyzer
Find Similar Products

Basic Info.

Model NO.
GDVA-405
Type
Transformer CT PT Analyzer
Accuracy Grade
1
Load Way
Electronic Load
Loading Method
Static Load
Display
Digital
Control
Manual Control
Weight
15kg
Power Source
AC220V
Product Name
Current Transformer Tester CT PT Analyzer
Usage
Transformer Tester
Test Standards
IEC60044-1/2/5/6
Voltage Output
0.1~180V (AC)
Current Output
0.001~5A(RMS)
Maximum Knee Voltage
45kv
Current Measurement Range
0~10A
Secondary Current
1A, 3A, 5A
Power Output
500va
Transport Package
Wooden Case
Specification
49*36*19cm
Trademark
GOLD
Origin
Chongqing, China
HS Code
9031809090
Production Capacity
200PCS/Month CT PT Analyzer

Product Description

Current Transformer Tester CT PT Analyzer
Current Transformer Tester CT PT Analyzer
Current Transformer Tester CT PT Analyzer
Current Transformer Tester CT PT Analyzer
Product Description
Current Transformer Tester CT PT Analyzer
CT PT Transformer Tester can fully test current and voltage transformers used in high-voltage substations, transmission lines and switchyards to verify ratings, troubleshoot faults and ensure reliability. By detecting defects and deviations from specifications, it can help power companies optimize performance, extend instrument life and ensure safety. It is suitable for many types of transformers such as Bushing Type CT, GIS CT, Through Type CT, HV CT, Measurement Type CT, and Protection CT.

 


Main Features
• Measure CT and PT ratios at high voltage levels
• Accurately measure phase shift and ratio error
• Automatic ratio and polarity testing for quick and easy testing
• Measure load and resistance of secondary windings
• Analyze transient performance response under abnormal conditions
• Large LCD screen for clear display of test results and parameters
• Compact, rugged design for substations and switchyards


Specifications

Test standards IEC60044-1, IEC60044-6, IEC60044-2, IEC60044-5, IEC61869,IEEE Std C57.13-2016
Power supply

 AC220V±10%, 50/60Hz±10%

(Support customize to AC110V,120V,127V)

Voltage output  0.1-180V (AC)
Current output  0.001-5A(RMS)
Power output  500VA
Max.  knee voltage measurement  60KV
Current measurement
 
 
  Range 0-10A (automatically change  range in 0.1/0.4/2/10A)
  Error  <±0.1%+0.01%FS
Voltage measurement
 
 Range 0-200V (automatically change range in 1V/10V/70V/200V)
 Error < ±0.1%+0.01%FS
Turns ratio measurement Range
  
1~35000
1~2000, error<0.05%
2000~5000,error<0.1%
5000~35000,error<0.2%
Phase measurement   error  ±2min
resolution  0.01min
Winding resistance measurement
    
   
Range 0-8kΩ (automatically change range in2ohm/20ohm/80ohm/800ohm/8kohm)
Error  < 0.2%RDG+0.02%FS
Maximum resolution :  0.1mΩ
Temperature measurement -50-100 Celsius degree; error<3 Celsius degree
CT Secondary burden Range 0-160ohm (automatically change range in 2ohm/20ohm/80ohm/160ohm)
Error  <0.2%RDG+0.02%FS
Maximum resolution : 0.001ohm
   
  
PT Secondary burden
 
Range 0-80kohm (automatically change range in 800ohm/8kohm/80kohm)
Error <0.2%RDG+0.02%FS
Maximum resolution : 0.1ohm
   
PT ratio measurement
Range

1-35000,

1-10000 error<0.1%, 

10000-35000 error<0.2%

PT ratio error measurement :Typical error<0.05%,  Maximum Error<0.1%
PT phase angle measurement maximum error < 3min
Memory capacity  >1000 groups test results
Working condition temperature  -10ºC-50ºC; moist ≤90%

Main Test Function

CT (protection, measurement) PT
Volt-ampere characteristic (excitation characteristic) curve Volt-ampere characteristic (excitation characteristic) curve
Automatically give the inflection point value Automatically give the inflection point value
Automatically give 5% and 10% error curves Transformation ratio measurement
Transformation ratio measurement Polarity judgment
Polarity judgment Ratio measurement
One flow test Angle difference measurement
Ratio measurement AC withstand voltage test
Angle difference measurement Secondary load test
AC withstand voltage test Secondary winding test
Secondary load test  Iron core demagnetization
Secondary winding test  
Iron core demagnetization  

 

Packing List
Current Transformer Tester CT PT Analyzer

Name  Quantity  Description
Host machine  1  
3M mask cable  2 Test cable for power out and CT
secondary
connection
10M mask cable 1 Test cable for CT primary connection
Grounding cable 1  
Big test pliers   2 One red and one black
Test gasket  4 Two red and two black
Test pin  4 Two red and two black
Test pliers 12 Three red and nine black
Short connection cable  1 Including six connection terminals
3A fuse 3  
Power cable 1  
Accessories bag  1  
Production disk 1 Include Analysis application and user manual
User manual 2  
Inspection report 1  
Pass certificate 1  
 
Packing and Delivery