Customization: | Available |
---|---|
After-sales Service: | Provide 1 Year After-Sales |
Warranty: | 1 Year for Transformer Oil Bdv Tester |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Transformer oil, a type of insulating and cooling oil used in transformers and other electrical equipment, needs to be tested periodically to ensure that it is still fit for purpose. This is because it tends to deteriorate over time. Testing sequences and procedures are defined by various international standards, many of them set by ASTM.Transformer oil testing consists of measuring breakdown voltage and other physical and chemical properties of samples of the oil, either in a laboratory or using portable test equipment on-site.
Introduction:
Features
Automatic laboratory oil test sets perform accurate breakdown voltage tests on mineral, ester and silicon insulating liquids. Moulded test vessels give repeatable results with lock in precision electrode gap setting adjustment wheels. The transparent, shielded lid and large test chamber enable easy access to the test vessel.
Specifications:
No. | Parameters | Specifications |
1 | Output voltage | AC 0~80KV (100KV for choice) |
2 | Rate of voltage rise | 0.5kv/s± 5%, 2kv/s± 5%, 3kv/s± 5%, 5kv/s± 5% |
3 | Max. test times | 9 |
4 | Stir time | 0~999s |
5 | Wait time | 0~999s |
6 | Measurement accuracy | ±(1% of full scale + 2 digits) |
7 | Resolution | 0.1KV |
8 | Oil Temperature measurement range | 0°C to 70°C, or better |
9 | Temperature resolution | 1°C, or better |
10 | Data storage | 100 groups |
11 | Weight | 41kg |
12 | Size | 620*430*330mm |
13 | Power supply | AC220V, 50Hz/60Hz |
14 | Working environment | Room temperature to 45°C, humidity<85% |
GDYJ Series Insulating Oil Dielectric Strength Tester
Model | GDYJ-501 | GDYJ-502 | GDYJ-502A |
Output Voltage | AC 0~80KV/0~100KV | AC 0~100KV | AC 0~80KV/0~100KV |
Rate of Voltage Rise | 2KV/s±10% | 0.5/2/3/5 KV/s±5% | 0.5/2/3/5 KV/s±5% |
Max. Time Setting | 0~9mins | 9mins | 0~99 seconds |
Test Precision | 3% RDG+0.3%FS | 3% RDG+0.3%FS | 1% of full scale +2digits |
Max. Data Storage | 100 groups | 100 groups | 100 groups |
Power Supply | AC220V±10% 50/60Hz | AC220V±10% 50/60Hz | AC220V±10% 50/60Hz |
Environment Temp. | 0~50Centigrade | 0~50Centigrade | 0~50Centigrade |
Related Humidity | <80%RH | <80%RH | <80%RH |
Dimension | 420*380*410mm | 620*430*330mm | 490*410*450mm |
Weight | 28kg | 41kg | 45kg |