Cheap Price CT Analyzer Current Transformer Tester CT PT Tester
A Transformer CT PT Tester, also known as a Current Transformer Potential Transformer Tester or CT PT Analyzer, is a specialized instrument used to test and analyze the performance of current transformers (CTs) and potential transformers (PTs).
Turns Ratio Test: The tester can measure the turns ratio of CTs and PTs, which is the ratio of the primary to secondary windings' turns. This test helps verify if the transformers are correctly designed and providing accurate current or voltage transformation.
Polarity Test: The tester verifies the polarity of the transformer windings to ensure they are connected correctly. Proper polarity is essential for accurate measurement and coordination with protective relays.
Ratio Error Test: This test determines the accuracy of the transformers by comparing the measured ratio to the rated ratio. Any deviation from the expected ratio can indicate a fault or degradation in the transformers' performance.
Excitation Curve Test: The tester measures the magnetization characteristics of the CTs and PTs by applying different voltages and recording the resulting currents. This test helps evaluate the saturation behavior and linearity of the transformers.
Burden Test: The tester measures the burden impedance of the CTs and PTs to ensure they fall within the specified limits. Burden impedance affects the accuracy and performance of the transformers under different load conditions.
Winding Resistance Test: The tester measures the resistance of the transformer windings to assess their condition and detect any potential faults like loose connections or high resistance joints.
Saturation Test: The tester checks the saturation characteristics of the transformers by applying increasing voltages until saturation occurs. This test helps determine the transformers' operating limits and performance under high-magnitude current or voltage conditions.
Demagnetization: The tester can perform a demagnetization process to remove any residual magnetism in the transformers.
GDVA-405 CT PT Analyzer | ||
1 | Test standards | IEC60044-1, IEC60044-6, GB1208, GB16847, C57.13 |
2 | Power supply | AC220V±10%,50Hz/60Hz±10% |
3 | Power output | 0.1~125V (AC) |
4 | Current output | 0.001~5A(RMS) |
5 | Power output | 300VA |
6 | Max. knee voltage measurement | 45kv |
7 | Current measurement range | 0~10A (automatically change range in 0.1/0.4/2/10A) |
8 | Current measurement error | <±0.1%+0.01%FS |
9 | Voltage measurement range | 0~200 V (automatically change range in 1V/10V/70V/200V) |
10 | Voltage measurement error | < ±0.1%+0.01%FS |
11 | Turns ratio measurement range | 1~30000; 1~2000 error<0.05%; 2000~5000 error>0.1%; 5000~35000 error<0.2% |
12 | Phase measurement | error:±2min,resolution:0.01min |
13 | Coil resistance measurement | Range: 0~8kΩ(automatically change range in 2ohm /20ohm /80ohm/800ohm/8kohm) Error< 0.2%RDG+0.02%FS Maximum resolution: 0.1mΩ |
14 | Temperature measurement | -50~100 Celsius degree, error<3 Celsius degree |
15 | CT Secondary burden | Range 0-160ohm (automatically change range in 2ohm/ 20ohm/80ohm/160ohm) Error <0.2%RDG+0.02%FS Maximum resolution 0.001ohm |
16 | PT Secondary burden | Range 0-80kohm (automatically change range in 800ohm / 8kohm /80kohm) Error <0.2%RDG+0.02%FS Maximum resolution: 0.1ohm |
17 | PT ratio measurement | Range: 1~30000, 1~5000 error<0.2% 5000~30000 error<0.5% |
18 | Saved data groups | >1000groups |
19 | Work condition | Temperature:-10ºC-50ºC, moist:≤90% |
20 | Gross Size | 70*50*41CM |
21 | Gross Weight | 40kg |
Standard configuration for CT/PT Analyzer:
Name | Quantity | Description |
Host machine | 1 | |
3M mask cable | 2 | Test cable for power out and CT secondary connection |
10M mask cable | 1 | Test cable for CT primary connection |
Grounding cable | 1 | |
Big test pliers | 2 | One red and one black |
Test gasket | 4 | Two red and two black |
Test pin | 4 | Two red and two black |
Test pliers | 12 | Three red and nine black |
Short connection cable | 1 | Including six connection terminals |
3A fuse | 3 | |
Power cable | 1 | |
Accessories bag | 1 | |
Production disk | 1 | Include Analysis application and user manual |
User manual | 2 | |
Inspection report | 1 | |
Pass certificate | 1 |