• Current and Voltage Transformer Diagnostic Device CT PT Tester
  • Current and Voltage Transformer Diagnostic Device CT PT Tester
  • Current and Voltage Transformer Diagnostic Device CT PT Tester
  • Current and Voltage Transformer Diagnostic Device CT PT Tester
  • Current and Voltage Transformer Diagnostic Device CT PT Tester
  • Current and Voltage Transformer Diagnostic Device CT PT Tester

Current and Voltage Transformer Diagnostic Device CT PT Tester

After-sales Service: Lifetime Technical Support
Warranty: 1 Year for Transformer CT PT Tester
Type: Transformer CT PT Tester
Accuracy Grade: 0.5
Load Way: Electronic Load
Loading Method: Dynamic Load
Samples:
US$ 7500/Piece 1 Piece(Min.Order)
| Request Sample
Customization:
Diamond Member Since 2007

Suppliers with verified business licenses

Manufacturer/Factory, Trading Company
  • Overview
  • Product Parameters
Overview

Basic Info.

Model NO.
GDVA-405
Display
Digital
Control
Fully Automatic
Weight
15kg
Power Source
AC220V
Product Name
Current Potential Transformer CT PT Analyzer
Usage
Transformer Tester
Test Standards
IEC60044-1/2/5/6
Voltage Output
0.1~180V (AC)
Current Output
0.001~5A(RMS)
Maximum Knee Voltage
45kv
Power Supply
220V 50Hz
Current Measurement Range
0~10A
Secondary Current
1A,3A,5A
Power Output
500va
Transport Package
Wooden Case
Specification
65*46*40CM
Trademark
GOLD
Origin
Chongqing, China
HS Code
9031809090
Production Capacity
200PCS/Month CT PT Analyzer

Product Description

GDVA-405 Current Transformer and Potential Transformer Tester CT PT Analyzer

Current and Voltage Transformer Diagnostic Device CT PT Tester


Main application scenarios:

  1. Parameter checking of the CT nameplate
  2. Parameter checking when the CT is connected to the current load
  3. Analysis of the influence of the transient characteristics of the CT on the relay protection device.
  4. Verification of the nameplate parameters of the PT
  5. Calibration of PT secondary load
 

Product Parameters

 

Test standard IEC60044-1/2/5/6
IEEE C57.13
Input power voltage AC220V±10%,45-65Hz
Output voltage and current 0.1-180V(AC RMS)
0.001-12A(AC RMS),36A(peak)
Maximum equivalent inflection point voltage 60KV
CT turns ratio measurement range: 1 to 40000,
1 to 2000 error <0.05%
2000 to 5000 error <0.1%
5000 to 40000 error <0.2%
CT ratio measurement typical error 0.02%, guaranteed error <0.1%
Phase measurement
 
accuracy: ±2min, resolution: 0.01min
CT and PT winding resistance measurement range range: 0 ~ 8KΩ (automatic range2Ω/20Ω/80Ω/800Ω/8KΩ), error<0.2%RDG+0.02%FS, maximum resolution: 0.1mΩ
Temperature measurement -50~100 degrees, error <3 degrees
CT secondary load measurement  0~160Ω(2/20/80Ω/160Ω), error 0.2%RDG+0.02%FS, max. resolution 0.001Ω
PT secondary load measurement
 
0~80kΩ(800Ω/8Ω/80Ω),
error 0.2%RDG+0.02%FS, max. resolution 0.1Ω
PT turns ratio measurement range: 1~30000,
1~2000 error <0.05%, 2000-5000 error <0.1%, 5000~30000 error <0.2%
PT ratio measurement range 1~2000, error 0.1%
PT angle difference measurement error<5min
Screen Display 12.1 inch large color screen display, touch screen way to achieve man-machine interaction
Data storage More than 5000 groups
Working conditions: temperature: -10ºC~50ºC,
humidity: ≤90%
Outline dimensions 485×356×183mm,
weight: 15Kg

More details for CT PT Analyzer----interface show

Current and Voltage Transformer Diagnostic Device CT PT Tester


Multi-faceted display
 

Current and Voltage Transformer Diagnostic Device CT PT Tester
Current and Voltage Transformer Diagnostic Device CT PT Tester

Standard configuration for CT/PT Analyzer

Name  Quantity  Description
Host machine  1  
3M mask cable  2 Test cable for power out and CT
secondary
connection
10M mask cable 1 Test cable for CT primary connection
Grounding cable 1  
Big test pliers   2 One red and one black
Test gasket  4 Two red and two black
Test pin  4 Two red and two black
Test pliers 12 Three red and nine black
Short connection cable  1 Including six connection terminals
3A fuse 3  
Power cable 1  
Accessories bag  1  
Production disk 1 Include Analysis application and user manual
User manual 2  
Inspection report 1  
Pass certificate 1  

Order & Customer Feedback:
Current and Voltage Transformer Diagnostic Device CT PT Tester
Our Company:
Current and Voltage Transformer Diagnostic Device CT PT Tester

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now

You Might Also Like

Diamond Member Since 2007

Suppliers with verified business licenses

Manufacturer/Factory, Trading Company
Registered Capital
100800000 RMB
Plant Area
>2000 square meters