CE Approved Transformer CT PT Testing Equipment CT PT Tester
Testing Items:
1. Turns ratio testing: Measuring the turns ratio of current transformers (CT) and potential transformers (PT), which is the ratio between the input signal and the output signal.
2. Phase angle testing: Measuring the phase difference between the input signal and the output signal to assess the phase accuracy of CTs and PTs.
3. Vector error testing: Evaluating the difference between the output and theoretical output of CTs and PTs to determine their vector error.
4. Frequency response testing: Checking the response characteristics of CTs and PTs at different frequencies to ensure accuracy and stability across different frequency ranges.
5. Load characteristic testing: Testing the output performance of CTs and PTs under different load conditions to verify their load adaptability and stability.
6. Insulation resistance testing: Evaluating the insulation performance of CTs and PTs, including measurement and assessment of insulation resistance.
7. Zero-sequence current testing: Measuring the response of CTs to zero-sequence currents to assess their capability to detect zero-sequence faults.
8. Withstand voltage testing: Conducting high-voltage withstand tests to verify the insulation strength and tolerance of CTs and PTs.
Specifications:
Item Name | GDVA-405 CE Approved Transformer CT PT Testing Equipment CT PT Tester | |
Test standards | IEC60044-1, IEC60044-6, IEC60044-2, IEC60044-5, C57.13 | |
Power supply | AC220V±10%, 50/60Hz±10% | |
Voltage output | 0.1~180V (AC) | |
Current output | 0.001~5A(RMS) | |
Power output | 500VA | |
Max. knee voltage measurement | 45KV | |
Current measurement |
Range | 0~10A (automatically change range in 0.1/0.4/2/10A) |
Error | <±0.1%+0.01%FS |
Voltage measurement |
Range | 0~200V (automatically change range in 1V/10V/70V/200V) | |
Error | < ±0.1%+0.01%FS | ||
Turns ratio measurement Range |
1~35000 1~2000, error<0.05% 2000~5000,error<0.1% 5000~35000,error<0.2% |
||
Phase measurement | error | ±2min | |
resolution | 0.01min | ||
Winding resistance measurement |
Range | 0~8kΩ (automatically change range in2ohm/20ohm/80ohm/800ohm/8kohm) | |
Error | < 0.2%RDG+0.02%FS | ||
Maximum resolution : 0.1mΩ | |||
Temperature measurement | -50~100 Celsius degree; error<3 Celsius degree | ||
CT Secondary burden | Range | 0~160ohm (automatically change range in 2ohm/20ohm/80ohm/160ohm) | |
Error | <0.2%RDG+0.02%FS | ||
Maximum resolution : 0.001ohm | |||
PT Secondary burden |
Error | 0~80kohm (automatically change range in 800ohm/8kohm/80kohm) | |
Maximum | <0.2%RDG+0.02%FS | ||
resolution | 0.1ohm | ||
PT ratio measurement |
Range |
1~35000, 1~10000 error<0.1%, 10000~35000 error<0.2% |
|
PT ratio error measurement :Typical error<0.05%, Maximum Error<0.1% | |||
PT phase angle measurement maximum error < 3min | |||
Make evaluation for test results according to selected standards Make word report for test result Make word reports one time for multi-group test records on the PC Calculate the ratio errors and phase angle errors at rated burden and working burden in one time test Compare excitation curves with saved excitation curves in the same window |
|||
Memory capacity | >1000 groups test results | ||
Working condition temperature | -10ºC~50ºC; moist ≤90% |