Customization: | Available |
---|---|
After-sales Service: | Lifetime Technical Support |
Warranty: | 1 Year for Current Transformer Tester CT PT Test |
Still deciding? Get samples of US$ 6000/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
GDVA-405 Portable Current Transformer Tester CT PT Test Set
CTs and PTs are used to measure and transform electrical currents and voltages in power systems to levels suitable for measurement and protection purposes. It is crucial to ensure the accuracy and reliability of these transformers to maintain the overall integrity of the power system.
A transformer CT/PT tester is designed to perform various tests to assess the performance of CTs and PTs.
Tests for Current Transformer: Tests for Potential Transformer:
1. Excitation curve and parameters test 1. Turns ratio test
2. Turns ratio test 2. Ratio error and phase angle error test
3. Ratio and phase error test 3. Polarity test
4. Polarity mark check 4. Secondary burden test
5. Winding resistance measurement 5. Winding resistance test
6. Secondary loop burden measurement
7. Error line curve test for protection CT
8. Transient CT parameters test
9. CT nameplate guess
10. Saturation hysteresis loop curve measurement
Applications of CT/ PT Analyzer:
Specification:
GDVA-405 CT PT Analyzer | ||
1 | Test standards | IEC60044-1, IEC60044-6, GB1208, GB16847, C57.13 |
2 | Power supply | AC220V±10%,50Hz/60Hz±10% |
3 | Power output | 0.1~125V (AC) |
4 | Current output | 0.001~5A(RMS) |
5 | Power output | 300VA |
6 | Max. knee voltage measurement | 45kv |
7 | Current measurement range | 0~10A (automatically change range in 0.1/0.4/2/10A) |
8 | Current measurement error | <±0.1%+0.01%FS |
9 | Voltage measurement range | 0~200 V (automatically change range in 1V/10V/70V/200V) |
10 | Voltage measurement error | < ±0.1%+0.01%FS |
11 | Turns ratio measurement range | 1~30000; 1~2000 error<0.05%; 2000~5000 error>0.1%; 5000~35000 error<0.2% |
12 | Phase measurement | error:±2min,resolution:0.01min |
13 | Coil resistance measurement | Range: 0~8kΩ(automatically change range in 2ohm /20ohm /80ohm/800ohm/8kohm) Error< 0.2%RDG+0.02%FS Maximum resolution: 0.1mΩ |
14 | Temperature measurement | -50~100 Celsius degree, error<3 Celsius degree |
15 | CT Secondary burden | Range 0-160ohm (automatically change range in 2ohm/ 20ohm/80ohm/160ohm) Error <0.2%RDG+0.02%FS Maximum resolution 0.001ohm |
16 | PT Secondary burden | Range 0-80kohm (automatically change range in 800ohm / 8kohm /80kohm) Error <0.2%RDG+0.02%FS Maximum resolution: 0.1ohm |
17 | PT ratio measurement | Range: 1~30000, 1~5000 error<0.2% 5000~30000 error<0.5% |
18 | Saved data groups | >1000groups |
19 | Work condition | Temperature:-10ºC-50ºC, moist:≤90% |
20 | Size | 70*50*41CM |
21 | Gross Weight | 40kg |
About CT/PT Analyzer Software:
Standard Configuration for CT/PT Analyzer:
Name | Quantity | Description |
Host machine | 1 | |
3M mask cable | 2 | Test cable for power out and CT secondary connection |
10M mask cable | 1 | Test cable for CT primary connection |
Grounding cable | 1 | |
Big test pliers | 2 | One red and one black |
Test gasket | 4 | Two red and two black |
Test pin | 4 | Two red and two black |
Test pliers | 12 | Three red and nine black |
Short connection cable | 1 | Including six connection terminals |
3A fuse | 3 | |
Power cable | 1 | |
Accessories bag | 1 | |
Production disk | 1 | Include Analysis application and user manual |
User manual | 2 | |
Inspection report | 1 | |
Pass certificate | 1 |