IEC Standard Insulating Oil Tester Bdv of Transformer Oil
Introduction:
♦
A large-screen LCD display, Chinese characters to show the measurement process and outcomes, a tiny printer to print different test data, audible signal prompts, and a completely automatic test procedure are all included.
♦
Keyboard shortcuts make it simple to enter and store test parameters including mixing time, standing time, and test timings.
♦
If not updated the following time, it won't go away after the power is turned off.
♦
Numerous testing have shown that this device is highly interference-resistant and accurate in measuring. dependable performance that is safe and stable.
Characteristics:
♦ Measure the voltage directly at its highest value to prevent having the test voltage waveform's distortion affect the validity of the test findings.
♦ By collecting the breakdown current directly from the high-voltage side, the conventional approach of sampling from the low-voltage side for overload protection is avoided, which results in significant mistakes.
♦ The specifically created low-voltage side control circuit uses single-chip microcomputer control inverter power supply technology, omitting the need for a motor, voltage regulator, and other parts. No mechanical wear, looseness, jamming, poor contact, etc., which are common with identical instruments, occur throughout the test. disadvantages, more dependable performance. The weight is lighter and the volume is less at the same time.
Technique index:
Rated power supply |
AC 220V±10% 50/60Hz |
Output voltage |
AC 0~80KV/AC 0~100KV |
Rate of voltage rise |
0.5/2/3/5KV/s±5% |
Measuring precision |
3 class |
Times |
1-9 |
Mixing time |
0~99 second |
Placing time |
0-9 minute 59second |
Save 100 groups of data most |
Voltage limit setting for proof test |
20KV-70KV |
Hold time for proof test |
1 minute-10 minutes |
Environment temperatures |
5-40ºC |
Relative humidity |
≤80%RH |
Size |
490*410*450mm |
Weight |
45kg |