After-sales Service: | Lifetime Technical Support |
---|---|
Warranty: | 1 Year for Hv Insulation Tester AC DC Hipot Tester |
Product Name: | High Voltage Insulation Tester AC DC Hipot Tester |
Application: | Oil Type Hipot Tester |
Usage: | Hipot Tester |
Standard: | T-9641-1999 |
Samples: |
---|
Customization: |
---|
Suppliers with verified business licenses
I.Introduction
II.Technique index of HIPOT TESTER
1. power supply:
AC220V 50Hz/60Hz for transformers which the capacity less than 10kva
AC380V 50Hz/60Hz for transformers which the capacity more than 10kva
2.HV transformer mode: single phase
3.maximum output voltage: 50kv/100kv/150kv/200kv/250kv optional
4.output capacity: 3kva/5kva/10kva/20kva/30kva/50kva/100kva/150kva/200kva optional
5.voltage read mode: analog or digital, direct HV voltage reading form voltmeter
6.current read mode: analog or digital, direct LV circuit current reading from amp meter
7.protection mode: LV circuit over current protection
8.voltage adjust mode: manual regulation
9.Rated frequency: 50Hz/60Hz
10.Automatic zero position lock unit to avoid wrong operation in HV output
11.work temperature: 0~50degree
12.work humidity: <80%
Parameters for HV transformer
Type |
Capacity KVA |
Low Voltage Input |
High Voltage Output |
No Load Current% |
Impedance |
Weight max Kg |
||
Voltage KV |
Current |
Voltage KV |
Current mA |
|||||
GDJ -1.5/50 |
1.5 |
200 |
7.5 |
50 |
30 |
4 |
10 |
22 |
GDJ -3/50 |
3 |
200 |
15 |
50 |
60 |
4 |
10 |
33 |
GDJ -6/50 |
6 |
200 |
30 |
50 |
120 |
4 |
10 |
53 |
GDJ -10/50 |
10 |
200 |
50 |
50 |
200 |
4 |
10 |
79 |
GDJ-10/100 |
10 |
400 |
25 |
100 |
100 |
4 |
10 |
98 |
Notice:
Suppliers with verified business licenses