  • CT PT Tester CT Volt-Ampere Characteristic Tester
  • CT PT Tester CT Volt-Ampere Characteristic Tester
  • CT PT Tester CT Volt-Ampere Characteristic Tester
  • CT PT Tester CT Volt-Ampere Characteristic Tester
  • CT PT Tester CT Volt-Ampere Characteristic Tester
  • CT PT Tester CT Volt-Ampere Characteristic Tester
Find Similar Products

Basic Info.

Model NO.
GDVA-402
Product Name
CT PT Tester CT Volt-Ampere Characteristic Tester
Usage
Transformer Tester
Test Standards
IEC60044-1/2/5/6
Voltage Output
0.1~180V (AC)
Current Output
0.001~5A(RMS)
Maximum Knee Voltage
45kv
Current Measurement Range
0~10A
Secondary Current
1A,3A,5A
Power Output
500va
Transport Package
Wooden Case
Specification
45*34*30cm
Trademark
GOLD
Origin
Chongqing
HS Code
9031809090
Production Capacity
200PCS/Month CT PT Analyzer

Product Description

CT PT Tester CT Volt-ampere Characteristic Tester

CT PT Tester CT Volt-Ampere Characteristic Tester


Introduction

CT PT volt-ampere characteristic phase ratio polarity tester is mainly used for on-site testing of protection-grade CT and PT. The tester is easy to operate, fully computerized equipment, high-performance CPU, no manual operation required, and the test is completed automatically to prevent personal contact with high-voltage circuits. The maximum output voltage of the volt-ampere characteristic test reaches 1000V, the maximum output current of the ratio test is 600A, and the output capacity of the internal voltage regulator is 5KVA. It uses an LCD display and is equipped with a small built-in printer for on-site printing. It supports the use of USB flash drives to download data, and is simple and convenient to operate.

Technical Index

1 Test standards IEC60044
2 Power supply AC220V±10%,50Hz/60Hz±10%
3 Power output 0.1~125V (AC)
4 Current output 0.001~5A(RMS)
5 Power output 3KVA
6 Max. knee voltage measurement 45kv
7 Current measurement range 0~10A (automatically change range in 0.1/0.4/2/10A)
8 Current measurement error <±0.1%+0.01%FS
9 Voltage measurement range 0~200 V (automatically change range in 1V/10V/70V/200V)
10 Voltage measurement error < ±0.1%+0.01%FS
11 Turns ratio measurement range 1~30000;
1~2000 error<0.05%; 2000~5000 error>0.1%; 5000~35000 error<0.2%
12 Phase measurement error:±2min,resolution:0.01min
13 Coil resistance measurement Range: 0~8kΩ(automatically change range in 2ohm /20ohm /80ohm/800ohm/8kohm)
Error< 0.2%RDG+0.02%FS Maximum resolution: 0.1mΩ
14 Temperature measurement -50~100 Celsius degree, error<3 Celsius degree
15 CT Secondary burden Range 0-160ohm (automatically change range in 2ohm/ 20ohm/80ohm/160ohm)
Error <0.2%RDG+0.02%FS Maximum resolution 0.001ohm
16 PT Secondary burden Range 0-80kohm (automatically change range in 800ohm / 8kohm /80kohm)
Error <0.2%RDG+0.02%FS Maximum resolution: 0.1ohm
17 PT ratio measurement Range: 1~30000, 1~5000 error<0.2% 5000~30000 error<0.5%
18 Saved data groups >1000groups
19 Work condition Temperature:-10ºC-50ºC, moist:≤90%
20 Size 70*50*41CM
21 Weight 40kg


Applications

1. Excitation curve and parameters test
2. Turns ratio test
3. Ratio and phase error test
4. Polarity mark check
5. Winding resistance measurement
6. Secondary loop burden measurement
7. Error line curve test for protection CT
8. Transient CT parameters test
9. CT nameplate guess
10. Saturation hysteresis loop curve measurement

Tests for Potencial Transformer :

1. Turns ratio test
2. Ratio error and phase angle error test
3. Polarity test
4. Secondary burden test
5. Winding resistance test


More details 

About CT/PT Analyzer software:

CT PT Tester CT Volt-Ampere Characteristic Tester

GDVA-405 Top-Rated Automatic Current Transformer and Potential Transformer CT PT Tester

CT PT Tester CT Volt-Ampere Characteristic Tester

 Standard configuration

Name  Quantity  Description
Host machine  1  
3M mask cable  2 Test cable for power out and CT
secondary
connection
10M mask cable 1 Test cable for CT primary connection
Grounding cable 1  
Big test pliers   2 One red and one black
Test gasket  4 Two red and two black
Test pin  4 Two red and two black
Test pliers 12 Three red and nine black
Short connection cable  1 Including six connection terminals
3A fuse 3  
Power cable 1  
Accessories bag  1  
Production disk 1 Include Analysis application and user manual
User manual 2  
Inspection report 1  
Pass certificate 1  
 
CT PT Tester CT Volt-Ampere Characteristic Tester

CT PT Tester CT Volt-Ampere Characteristic Tester
Order & Customer Feedback:
CT PT Tester CT Volt-Ampere Characteristic Tester

 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now
Contact Supplier