• Multifunctional Transformer CT PT Tester Current Transformer Tester
  • Multifunctional Transformer CT PT Tester Current Transformer Tester
  • Multifunctional Transformer CT PT Tester Current Transformer Tester
  • Multifunctional Transformer CT PT Tester Current Transformer Tester
  • Multifunctional Transformer CT PT Tester Current Transformer Tester
  • Multifunctional Transformer CT PT Tester Current Transformer Tester

Multifunctional Transformer CT PT Tester Current Transformer Tester

After-sales Service: Lifetime Technical Support,Online Service
Warranty: 12 Months
Power: Electronic
Test Standards: IEC60044-1, IEC60044-6, IEC60044-2, IEC60044-5, C5
Voltage Output: 0.1~180V (AC)
Current Output: 0.001~5A(RMS)
Customization:
Diamond Member Since 2007

Suppliers with verified business licenses

Manufacturer/Factory, Trading Company

Basic Info.

Model NO.
GDVA-405
Power Output
500va
Maximum Knee Voltage Measurement
45kv
Product Name
Multifunctional Transformer CT PT Tester
Current Measurement Range
0~10A (Automatically Change Range in 0.1/0.4/2/10
Current Measurement Error
<±0.1%+0.01%Fs
Transport Package
Wooden Case
Specification
CT PT Tester
Trademark
GOLD
Origin
Chongqing, China (Mainland)
HS Code
9031809090
Production Capacity
50sets / Month

Product Description

Multifunctional Transformer CT PT Tester Current Transformer Tester


Introduction:
 
Tests for Current Transformer:  Tests for Potencial Transformer: 
1 Excitation curve and parameters test
2 Turns ratio test
3 Ratio and phase error test
4 Polarity mark check
5 Winding resistance measurement
6 Secondary loop burden measurement
7 Error line curve test for protection CT
8 Transient CT parameters test
9 CT nameplate guess
10 Saturation hysteresis loop curve measurement
1 Turns ratio test
2 Ratio error and phase angle error test
3 Polarity test
4 Secondary burden test
5 Winding resistance test 


Applications of CT/ PT Analyzer:  
1 CT nameplate check
2 CT parameters check in work burden
3 CT transient parameters analysis
4 CT ratio and phase error calibration
5 PT routine test 


Technical index:
1 Test standards: IEC60044-1, IEC60044-6, IEC60044-2, IEC60044-5, C57.13
2 Power supply: AC220V±10%, 50/60Hz±10%
3 Voltage output: 0.1~180V (AC)
4 Current output: 0.001~5A(RMS)
5 Power output: 500VA
6 Maximum knee voltage measurement: 45KV
7 Current measurement:
  Range: 0~10A (automatically change range in 0.1/0.4/2/10A)
  Error: <±0.1%+0.01%FS
8 Voltage measurement:
  Range: 0~200V (automatically change range in 1V/10V/70V/200V)
 Error: < ±0.1%+0.01%FS
9 Turns ratio measurement:
  Range: 1~35000
 1~2000 error<0.05%
 2000~5000 error<0.1%
 5000~35000 error<0.2%
10 Phase measurement: error: ±2min; resolution: 0.01min
11 Winding resistance measurement:
  Range: 0~8kΩ (automatically change range in 2ohm/20ohm/80ohm/800ohm/8kohm)
 Error: < 0.2%RDG+0.02%FS
 Maximum resolution: 0.1mΩ
12 Temperature measurement: -50~100 Celsius degree; error<3 Celsius degree
13 CT Secondary burden:
  Range: 0~160ohm (automatically change range in 2ohm/20ohm/80ohm/160ohm)
 Error: <0.2%RDG+0.02%FS
  Maximum resolution: 0.001ohm
14 PT Secondary burden:
  Range: 0~80kohm (automatically change range in 800ohm/8kohm/80kohm)
 Error: <0.2%RDG+0.02%FS
  Maximum resolution: 0.1ohm
15 PT ratio measurement:
  Range: 1~35000
 1~10000 error<0.1%
 10000~35000 error<0.2%
16 PT ratio error measurement: Typical error <0.05%, Maximum Error<0.1%
17 PT phase angle measurement: maximum error < 3min
18 Make evaluation for test results according to selected standards
19 Make word report for test result
20 Make word reports one time for multi-group test records on the PC
21 Calculate the ratio errors and phase angle errors at rated burden and working burden in one time test
22 Compare excitation curves with saved excitation curves in the same window
23 Memory capacity: >1000 groups test results
24 Working condition: temperature: -10ºC~50ºC; moist: ≤90%  
Multifunctional Transformer CT PT Tester Current Transformer Tester

Multifunctional Transformer CT PT Tester Current Transformer Tester
Multifunctional Transformer CT PT Tester Current Transformer TesterMultifunctional Transformer CT PT Tester Current Transformer Tester
Multifunctional Transformer CT PT Tester Current Transformer Tester

 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now

You Might Also Like

Diamond Member Since 2007

Suppliers with verified business licenses

Manufacturer/Factory, Trading Company
Registered Capital
100800000 RMB
Plant Area
>2000 square meters