After-sales Service: | Lifetime Technical Support |
---|---|
Warranty: | 1 Year for 6 Phase Relay Protection Tester |
Type: | 6 Phase Relay Protection Tester |
Accuracy Grade: | 0.2% |
Load Way: | Electronic Load |
Loading Method: | Dynamic Load |
Samples: |
---|
Customization: |
---|
Suppliers with verified business licenses
Embedded host machine, equipped with big programmed CPLD(Complex Programmable Logic Device);
12channels D/A output simultaneously in a single machine;
Meets all the requirement of field tests. Digital Signal Processor Microcomputer. Not only test the traditional relays and protectors, but also test the modern microcomputer relays, special for transformer differential protection and transfer equipment.
The main control board is DSP + FPGA architecture, 16 bit DAC output, generates high - density sine wave 2000 points each circle to fundamental wave, which greatly improve the wave quality and the accuracy of the test instrument.
Using high-fidelity linear amplifier. Both to ensure the accuracy of a low current, but also guarantee the stability of the high current.
High precise linear power amplifier,6 voltage outputs and 6 current outputs;
8 inch LCD screen display. Provide with keyboard/mouse connecting port,also 2USB port,2 RS232 port,to communicate with PC and other communication devices;
Easy to carry,suitable for flexible testing and wild working;
Intelligent self-protection;
8 channels switching value input and 4channels switching value output.Input contact is idle contact and 0-250V potential contact for selectable, intelligent identification;
Plentiful Binary and powerful software function;
Two groups of DC power supply, 110VDC/1.0A&220VDC/0.6A,no need to set and adjust by software(Optional);
Single phase current output (RMS) | 0 -- 30A / phase, accuracy: 0.2% ± 5mA |
six phase parallel output (RMS) | 0 - 180A / 6 same phase parallel output |
Allowable working value of phase current for a long time (effective value) | 10A |
Maximum output power per phase | 300VA |
Maximum output power of six phase parallel current | 1000VA |
Six and the maximum output current allowed working time | 5s |
frequency range | 0 -- 1000Hz, accuracy 0.001Hz |
Harmonic number | 2--20second |
phase | 0--360The accuracy is 0.1 degree |
DC current output | 0--± 10A / phase, accuracy: 0.5% ± 5mA |
Single phase voltage output (RMS) | 0 -- 125V / phase, accuracy: 0.2% ± 5mv |
Line voltage output (RMS) | 0--250V |
Phase voltage / line voltage output power | 75VA/100VA |
frequency range | 0 -- 1000Hz, accuracy: 0.001Hz |
Harmonic number | 2--20second |
phase | 0--360Degree, accuracy: 0.1 degree |
Single phase voltage output amplitude | 0--± 150V, accuracy: 0.2% ± 5mv |
Output amplitude of line voltage | 0--±300V |
Phase voltage / line voltage output power | 90VA/180VA |
Switch input terminal | 8yes |
Air contact | 1 -- 20 mA, 24 V, internal active output of the device |
Potential reversal | Passive contact: low resistance short circuit signal Active contact: 0-250V DC |
Switch output terminal | 4Yes, no contact, breaking capacity: 110V / 2a, 220V / 1a |
time frame | 1ms -- 9999s, measuring accuracy: 1ms |
Volume and weight of single machine | Volume 410 x 190 x 420mm3, about 18kg |
Power Supply | AC220V±10%,50Hz,10A |
Suppliers with verified business licenses