• Non-Combustibility Test Apparatus for Building Materials ISO 1182 BS 476-4 BS 476-11
  • Non-Combustibility Test Apparatus for Building Materials ISO 1182 BS 476-4 BS 476-11
  • Non-Combustibility Test Apparatus for Building Materials ISO 1182 BS 476-4 BS 476-11
  • Non-Combustibility Test Apparatus for Building Materials ISO 1182 BS 476-4 BS 476-11
  • Non-Combustibility Test Apparatus for Building Materials ISO 1182 BS 476-4 BS 476-11
  • Non-Combustibility Test Apparatus for Building Materials ISO 1182 BS 476-4 BS 476-11

Non-Combustibility Test Apparatus for Building Materials ISO 1182 BS 476-4 BS 476-11

After-sales Service: All Life Technical Supports
Warranty: 12 Months
Item Name: Non-Combustibility Test Apparatus
Reference Standards: ISO 1182 BS 476-4 BS 476-11
Power: 220 V AC, 60 Hz, 10A
Size: 400(W) *400(D) * 1270(H)mm
Customization:
Diamond Member Since 2007

Suppliers with verified business licenses

Manufacturer/Factory, Trading Company

Basic Info.

Model NO.
GD-ISO1182
Utilities
Personal Computer and PC Printer
Control Unit
530(W) * 270(D) * 280(H)mm
Single Zone Furnace Operable
at up to 900 Degree
Furnace Facilitating
Maintenance and Replacement
RS 232c Communication
Daq Board-Adopted Interface
Alarm Temperature-Based
Over Current Shut-off System
Manual
Provide
Transport Package
Plywood Case
Trademark
GOLD
Origin
Chongqing China(Mainland)
HS Code
9031809090
Production Capacity
500 Sets/ Year

Product Description

Non-combustibility Test Apparatus for Building Materials ISO 1182 BS 476-4 BS 476-11
Non-Combustibility Test Apparatus for Building Materials ISO 1182 BS 476-4 BS 476-11

Introduction:

Non-Combustibility Tester measures the incombustibility and combustibility of uniform building material and non-uniform building material of actual element.

The evaluations (results) are rising temperature in the furnace, basic mass loss, and ignition of a specimen.

It fully satisfies KS F 2271, KS F ISO 1182, and ISO 1182 as international standards at the same time.

This equipment uses a module-type temperature controller to be stable over 60 minutes in the furnace condition of 750±5ºC and meets precise test results.

And another advantage is the automatic up-down specimen movement device for accurate results as well as a user-friendly process. Thus, it doesn't matter who is test-users.

RS 232C communication and Data Acquisition Board is able to be an accurate Interface of test values, so users can test the whole function and test by PC easily and automatically.

Application:

* Building Materials

* Rail

* IMO

Standards:

1. ISO 1182: Reaction to fire test for building material---Non-combustibility test

2. BS 476-4 : Fire Tests on Building Materials and Structures.. Part 4: Non-Combustibility Test for Materials

3. BS 476-11: Fire tests on building materials and structures - Part 11: Method for assessing the heat emission from building materials.

4. KS F ISO 1182: Method of a non-combustibility test of building products

5. KS F 2271: a Testing method for incombustibility of internal material and element of building
 

Feature:

1.  Single Zone Furnace operable at up to 900 ºC with the NIKROTHAL Ribbon Heater

2.  750±5ºC temperature auto control with TPR

3.  Furnace facilitating maintenance and replacement

4.  Up/down automatic moving system for correct positioning of the test sample and user's convenience

5.  Mirror to observe the ignition quality of the test sample

6.  RS 232C communication and DAQ Board-adopted interface   

7.  Auto testing by DAQ Board and PC

8.  Alarm temperature-based over current shut-off system for user's safety

9.  Software (Non-Comb 2005) to print out reports based on exact data result and each standard

Test Result:

* Mass Loss(g) and Rate(%)

* Ignition Time(s) and Sustained Flaming(s)

* Initial & Maximum Furnace Temperature(ºC)

* Final Furnace Temperature(ºC)

* Maximum Specimen Center Temperature(ºC)

* Final Specimen Center Temperature(ºC)

* Furnace Temperature Rise(ºC)

* Specimen Center & Surface Temperature Rise(ºC)

* Differential Test Result by Standards

(ISO 1182:1990, KS F ISO 1182: 2004, IMO FTPC Pt.1: 1998, KS F 2271: 1998) 

Specifications:

Size 400mm(w) × 40mm0(D) × 1,270mm(H)
Power 220 V AC, 60 Hz, 10 A
Weight about 40kg
control unit 530mm(w) × 270mm(D) × 280mm(H)
Manual supplied
Utilities Personal Computer and PC Printer


 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.