Gdrz-902 Sfra  Test Kit Deformation of Transformer Windings Tester

Product Details
Customization: Available
Sweep Modes: Linear Sweep, Section Sweep
Test Range: (-100dB)-(+20dB)
Diamond Member Since 2007

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

Registered Capital
100800000 RMB
Plant Area
>2000 square meters
  • Gdrz-902 Sfra  Test Kit Deformation of Transformer Windings Tester
  • Gdrz-902 Sfra  Test Kit Deformation of Transformer Windings Tester
  • Gdrz-902 Sfra  Test Kit Deformation of Transformer Windings Tester
  • Gdrz-902 Sfra  Test Kit Deformation of Transformer Windings Tester
Find Similar Products

Basic Info.

Model NO.
GDRZ-902
Test Accuracy
<0.01%
Signal Input Impedance
>1mΩ
Signal Output Impedance
50Ω
Standard
Dl/T911 2004
Transport Package
Standard Wooden Case
Trademark
GOLD
Origin
China
Production Capacity
500sets/Month

Product Description

PRODUCT DESCRIPTION
GDRZ-902 SFRA Test Kit Deformation of Transformer Windings Tester 

GDRZ-902  Frequency Response Analysis on Power Transformers is a powerful and sensitive method to evaluate the mechanical integrity of core, windings and clamping structures within power transformers by measuring their electrical transfer functions over a wide frequency range. SFRA is a proven method for frequency measurements.

Introduction:

  • The structure and reference of the transformer is fixed after been made, Therefor, the frequency response of each winding will be almost the same normally.
  • Some case such as cut off between circles or phases in experience, cut off or winding moved for the pull of power in running, winding moved for hit in transportation, could change the reference of the transformer ,of which the frequency response will be changed, we could detect the deformation according to the frequency response curve.
  • Our company has designed the winding deformation tester base on the idea and the advanced technique.
  •  Frequency Response Analysis on Power Transformers could draw the frequency response curve accurately. Then we compare the curves horizontally or vertically to detect the deformation of the transformer.
  •  Frequency Response Analysis on Power Transformers is conformed to the standard of DL/T911 2004.

Specifications:

 Frequency Response Analysis on Power Transformers
GDRZ-902 Transformer SFRA Sweep Frequency Response Analyzer
Two different sweep modes: Linear sweep, Section sweep
Linear Sweep 0.5KHz - 1MHz interval 0.5KHz 2000 dots
Section Sweep 50Hz - 100Hz interval 2Hz 25 dots
100HZ -1KHz interval 20Hz 45 dots
1KHz - 10KHz interval 50Hz 180 dots
10KHz - 100KHz interval 0.2KHz 450 dots
100KHz - 500KHz interval 0.5KHz 800 dots
500KHz - 1000KHz interval 1KHz 500 dots
Test Range (-100dB) - (+20dB)
Test Accuracy 0.1dB
Frequency Accuracy <0.01%
Signal Input Impedance >1M Ω
Signal Output Impedance 50 Ω

Gdrz-902 Sfra&#160; Test Kit Deformation of Transformer Windings Tester

OUR COMPANY

CHONGQING GOLD MECHANICAL & ELECTRICAL EQUIPMENT CO., LTD
 

We are making effort to develop together with customers from both domestic and abroad on the basis of reciprocity.
 

Chongqing Gold Mechanical&Electrical Equipment Co.,Ltd.  mainly design and manufacture the oil purifier and electrical testing equipment for more than 10 years.

After several years' development, our products have become high intelligent and wide coverage. And our company has become one of the leading manufacturer of oil purifier and electrical testing equipment in China;

We have developed sales channels in many countries such as UAE, Saudi Arabia, Iran, Malaysia, Thailand, Pakistan, India, Germany, Belgium, USA, Mexico, Kenya, Nigeria, South Africa and other countries worldwide.

And we have gained strong advantage and high reputation in international market.

We have persisted on the business idea of "Integrity Basis and Quality First" for the stable and constant development. We are making effort to develop together with customers from both domestic and abroad on the basis of reciprocity. Client, quality and service are our supreme target!
Gdrz-902 Sfra&#160; Test Kit Deformation of Transformer Windings Tester
Gdrz-902 Sfra&#160; Test Kit Deformation of Transformer Windings Tester
CONTACT US

 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now
Contact Supplier