Customization: | Available |
---|---|
After-sales Service: | Lifetime Technical Support |
Warranty: | 1 Year for Current and Potential Transformer Test |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Current Transformer Potential Transformer Test Instrument CT PT Tester
The CT PT tester is an electronic instrument used to calibrate and verify these transformers, providing accurate and automated testing capabilities for current and voltage transformers. The CTPT transformer is a key component that steps down high currents and voltages to safer levels for measurement, protection and control purposes. It has a DSP data acquisition system that can complete data acquisition for variable frequency power supply control and test processes.
* Higher accuracy and test stability.
* The tester has a wider range of functions.
* Larger storage capacity, more than 5000 groups.
* Simple operation, data analysis, storage and interface display are all completed by the industrial computer system.
Main Test items
Tests for CT | Tests for CP |
1. Excitation curve and parameters test | 1. Turns ratio test |
2. Turns ratio test | 2. Ratio error and phase angle error test |
3. Ratio and phase error test | 3. Polarity test |
4. Polarity mark check | 4. Secondary burden test |
5. Winding resistance measurement | 5. Winding resistance test |
6. Secondary loop burden measurement | |
7. Error line curve test for protection CT | |
8. Transient CT parameters test | |
9. CT nameplate guess | |
10. Saturation hysteresis loop curve measurement |
Applications
1. CT nameplate check
2. CT parameters check in work burden
3. CT transient parameters analysis
4. CT ratio and phase error calibration
5. PT routine test
Specifications
1 | Test Standards | IEC60044-1, IEC60044-6, IEC60044-2, IEC60044-5, IEC61869,C57.13 |
2 | Power supply | AC220V±10%, 50/60Hz±10%(Support customize) |
3 | Voltage output | 0.1-180V (AC) |
4 | Current output | 0.001-5A(RMS) |
5 | Power output | 500VA |
6 | Max. knee voltage measurement | 60KV |
7 | Current measurement | Range: 0-10A (automatically change range in 0.1/0.4/2/10A),
Error: <±0.1%+0.01%FS |
8 | Voltage measurement | Range:0-200V (automatically change range in 1V/10V/70V/200V).
Error: < ±0.1%+0.01%FS |
9 | Turns ratio measurement Range | 1-35000 1-2000, error<0.05% 2000-5000,error<0.1% 5000-35000,error<0.2% |
10 | Phase measurement | Error:±2min
Resolution: 0.01min |
11 | Winding resistance measurement |
Range: 0-8kΩ (automatically change range in 2 ohm/20 ohm/80 ohm/800 ohm/8 kohm). Error: < 0.2%RDG+0.02%FS. Max resolution : 0.1mΩ. |
12 | CT Secondary burden | Range: 0-160ohm (automatically change range in 2ohm/20ohm/80ohm/160ohm).
Error: <0.2%RDG+0.02%FS. Max resolution : 0.001ohm. |
13 | PT Secondary burden | Range:0-80kohm (automatically change range in 800ohm/8kohm/80kohm).
Error: <0.2%RDG+0.02%FS Max resolution : 0.1ohm. |
14 | PT ratio measurement range |
1-35000, 1-10000, error<0.1%, 10000-35000, error<0.2% |
15 | PT ratio error measurement | Typical error<0.05%, Max Error<0.1% |
16 | PT phase angle measurement | max error: < 3min |
Standard configuration
Name | QTY | Description |
Host machine | 1 | |
3M mask cable | 2 | Test cable for power out and CT secondary connection |
10M mask cable | 1 | Test cable for CT primary connection |
Grounding cable | 1 | |
Big test pliers | 2 | One red and one black |
Test gasket | 4 | Two red and two black |
Test pin | 4 | Two red and two black |
Test pliers | 12 | Three red and nine black |
Short connection cable | 1 | Including six connection terminals |
3A fuse | 3 | |
Power cable | 1 | |
Accessories bag | 1 | |
Production disk | 1 | Include Analysis application and user manual |
User manual | 2 | |
Inspection report | 1 | |
Pass certificate | 1 |