Gold Member Since 2007
Audited Supplier
Chongqing Gold Mechanical & Electrical Equipment Co., Ltd.

Tan Delta Test Set, Oil Tan Delta Tester, Tan Delta Test Kit manufacturer / supplier in China, offering Insulating Oil Tan Delta Tester Oil Cup Test-Bridge for Dielectric Loss, Cone Calorimeter ISO5660, Gd-4508c Bitumen Ductility Testing Machine and so on.

(/ )

Supplier Homepage Product Electrical Testing Equipment Insulating Oil Tan Delta Tester Oil Cup Test-Bridge for Dielectric Loss

Insulating Oil Tan Delta Tester Oil Cup Test-Bridge for Dielectric Loss

FOB Price: US $5 / Piece
Min. Order: 1 Piece
Min. Order FOB Price
1 Piece US $5/ Piece
Get Latest Price
Port: Chongqing, China
Production Capacity: 100PCS/Month
Payment Terms: L/C, T/T, Western Union, Money Gram

Request a custom order and have something just for you!

Send Customized Request
Basic Info
  • Model NO.: GDGY
  • Apparatus: Transformer Oil Dielectric Loss Tan Delta Tester
  • Device: Insulating Oil Tan Delta Tester
  • Capacitor Measurement Error: < 1%Rdg+0.5PF
  • Frequency: 50Hz/60Hz
  • Instrument Weight: <18kg
  • Transport Package: Wooden Case
  • Origin: Chongqing of China
  • Application: Automatic Insulating Oil Tan Delta Oil Tester
  • Function: Transformer Oil Tan Delta Testing Equipment
  • Tangent Delta Measurement Error: < 1%Rdg+0.02%
  • High Voltage Output: 1000~2000V
  • Size: 450mm*360mm*310mm
  • Trademark: Gold
  • Specification: ISO
  • HS Code: 9031809090
Product Description
GDGY Insulating Oil Tan Delta Tester Oil Cup Test-Bridge for Dielectric Loss


I. Introduction

GDGY Insulating Oil Tan Delta Tester is dedicated to insulating oil liquid medium of dielectric loss angle and volume resistivity testing of high precision instruments.


II. Features

1  Light weight, small size, test safe operation, a complex dual-use, portable integrated structure.
2  With all-digital technology, the operation is intelligent and automatic;
3  With a large screen (240 * 180) LCD display;
4  Test results can be printed out;
5  Easy operation, the operators without professional training can be skilled use.
6  One heating part adopts the most advanced of the current high-frequency induction heating method, the heating oil-cup with non-contact with the heater, heating evenly, fast and convenient control and so on.
7  AC Test Power Supply with AC-DC-AC conversion means, effectively prevent the mains voltage and frequency fluctuations of the dielectric loss test the accuracy of the impact of even the generator, the instrument can also be run correctly.
8  Internal standard capacitors SF6 inflatable 3-pole capacitor, the capacitor dielectric loss and electrical capacity is not the ambient temperature, humidity, etc., to guarantee precision equipment in line even after prolonged use.


III. Internal Integration

1  Dielectric loss oil cup;
2  temperature controller;
3  temperature sensor;
4  dielectric loss test bridge;
5  AC high voltage test power supply;
6  standard capacitors;
7  high impedance meter
8  DC high voltage test power supply and other major components.

IV. Main Technical Specs
 
1Condition of Use-5ºC_40ºC         RH<80%
2Power SourceAC 220V±10%      Without Frequency Limit
3High Voltage Output1000V_2200V      Every 200V
 Precision2%
 Capacity50VA               Output Current 25mA
4Temperature Control Induction StoveMaximal Power  500W
5TemperatureControl Range<100ºC
6Temperature Measuring Error±0.5ºC
7Control Temperature Error±1ºC
8Control Temperature TimeRoom Temperature 90ºC          <20min
9Measuring Rangetgδ         Without Limit
  Cx         15PF-300PF
  Rx          10M-10T
10PrecisionΔtgδ:
ΔCx :
ΔRx :
±(Reading*1.0%+0.020%)
±(Reading*1.0%+0.5PF)
±Reading *  10%
11Relative Dielectric Loss Constantεr   Calculated Automatically
12Volume Resistivityρ    Calculated Automatically
13Dimension450(L)×310(W)×360(H)
14Weight18Kg


 
Send your message to this supplier
Avatar
Miss Daisy Tao
Sales
*From:
To: Miss Daisy Tao
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now