Gold Member Since 2007
Audited Supplier
Chongqing Gold Mechanical & Electrical Equipment Co., Ltd.

Tangent Delta Tester, Insulating Oil Tangent Delta Tester, Transformer Oil Tangent Delta Tester manufacturer / supplier in China, offering Gdgy Insulating Oil Dielectric Loss Tangent Delta Tester, Gd-12579 ASTM D892 Lubrication Oil Foam Performance Tester, ASTM D2872 Asphalt Rolling Thin Film Oven Test Rtfot and so on.

(/ )

Supplier Homepage Product Electrical Testing Equipment Gdgy Insulating Oil Dielectric Loss Tangent Delta Tester

Gdgy Insulating Oil Dielectric Loss Tangent Delta Tester

Purchase Qty.:
(Pieces)
1 2+
FOB Unit Price: US $2 US $1
Purchase Qty. (Pieces) FOB Unit Price
1 US $2
2+ US $1
Get Latest Price
Port: Chongqing, China
Production Capacity: 50pieces/Month
Payment Terms: L/C, T/T, Western Union

Request a custom order and have something just for you!

Send Customized Request
Basic Info
  • Model NO.: GDGY
  • Temperature Control Induction Stove: Maximal Power 500W
  • Temperature Measuring Error: ±0.5ºC
  • Control Temperature Error: 0.1ºC
  • Relative Dielectric Loss Constant: Calculated Automatically
  • Trademark: Gold
  • Specification: 20kg
  • HS Code: 9031809090
  • AC High Voltage Output: 400V-2200V ±2% Every 100V 50va
  • Temperature Control Range: <100ºC
  • Condition of Use: -5ºC-40ºC Rh<80%
  • Control Temperature Time: Room Temperature 90ºC <20min
  • Product Name: Dielectric Loss Tester
  • Transport Package: Standard Wooden Case
  • Origin: Chongqing, China
Product Description
1.GDGY Digital Automatic Dielectric Dissipation Factor Tester is a high-precision instrument, which can be applied to measure dielectric loss angle and Volume Resistivity of insulating oil etc.

2.It is integrated by oil cup for dielectric loss, temperature-control equipment, temperature sensor, test-bridge for dielectric loss, AC trial electrical source, standard capacitor, high resistance meter and DC high-voltage power etc. 
The most advanced heating mode of high frequency induction is applied to the heating part of this instrument, which has the advantage of non-contact of oil cup and heating unit, homogeneous heating, quick velocity and convenient control etc. 

3.AC-DC-AC conversion mode is applied to AC trial electrical source so that the problem how to measure correctly under the fluctuation of voltage and frequency can be avoided. 

4.Even when the electric generator is working, the instrument can operate correctly.

5.The inner standard capacitor is SF6 three-pole inflate capacitor, whose dielectric loss and capacitance is not influenced by environmental temperature and dampness etc. 

6.In this way, the accuracy of the instrument is guaranteed conformably after a long-time application.

Main Specifications:
1.Condition of Use: -5ºC_40ºC RH<80%
2.Power Source:  AC 220V±10% Without Frequency Limit
3.High Voltage Output: 1000V_2200V Every 200V
            Precision: 2%
            Capacity : 50VA Output Current 25mA
4.Temperature Control Induction Stove:  Maximal Power 500W
5.TemperatureControl Range:  <100ºC
6.Temperature Measuring Error:  ±0.5ºC
7.Control Temperature Error:  ±1ºC
8.Control Temperature Time:  Room Temperature 90ºC <20min
9.Measuring Range:  tgδ    Without Limit
                    Cx       15PF-300PF
                    Rx       10M-10T
10. Precision:   Δtgδ:±(Reading*1.0%+0.020%)
                ΔCx :±(Reading*1.0%+0.5PF)
                ΔRx :±Reading * 10%
11.Relative Dielectric Loss Constant :        εr              Calculated Automatically
12.Volume Resistivity:          ρ           Calculated Automatically
13.Dimension:  450(L)×310(W)×360(H)
14.Weight:  18Kg
Send your message to this supplier
Avatar
Ms. Christine Gou
Sales
*From:
To: Ms. Christine Gou
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now