• Automatic CT PT Analyzer CT Meter Transformer CVT Test Machine
  • Automatic CT PT Analyzer CT Meter Transformer CVT Test Machine
  • Automatic CT PT Analyzer CT Meter Transformer CVT Test Machine
  • Automatic CT PT Analyzer CT Meter Transformer CVT Test Machine
  • Automatic CT PT Analyzer CT Meter Transformer CVT Test Machine
  • Automatic CT PT Analyzer CT Meter Transformer CVT Test Machine

Automatic CT PT Analyzer CT Meter Transformer CVT Test Machine

After-sales Service: Lifetime Technical Support
Warranty: 1 Year for CT PT Analyzer
CT PT Analyzer Application: Current Transformer & Voltage Transformer Testing
CT PT Analyzer Features: Fully Automatic, Multi-Function, Touch Screen
Standards: IEC60044-1/6/2/5, IEC61869, C57.13
Current Output: 0.001-5A(RMS)
Customization:
Diamond Member Since 2007

Suppliers with verified business licenses

Manufacturer/Factory, Trading Company
  • Overview
  • Product Description
  • Test Items
  • Technical Parameter
  • Testing Site
  • About Us
Overview

Basic Info.

Model NO.
GDVA-405 CT PT Analyzer
Power Output
500va
Test Accuracy
0.02%(Typical),0.1%(Guarantee)
Max Knee Point Voltage
60kv
Turns Ratio Measurement Range
1-35000
Net Weight
15kg
Service
Engineer Available to Service Overseas
Transport Package
Packed in Plywood Case
Specification
39kg gross weight
Trademark
GOLD
Origin
Chongqing, China
HS Code
9031809090
Production Capacity
1000 Sets/ Month

Product Description


GDVA-405 Automatic CT PT Analyzer CT Meter Transformer CVT Test Machine
 

Product Description

 

Automatic CT PT Analyzer CT Meter Transformer CVT Test Machine

The GDVA-405 CT PT Analyzer is an advanced and state-of-the-art professional instrument specifically engineered to provide comprehensive testing and analysis capabilities for current transformers (CTs) and potential transformers (PTs). With its cutting-edge technology and precise measurement capabilities, this instrument plays a crucial role in the industry by facilitating accurate assessment and evaluation of transformer performance.

Built with the latest advancements in testing equipment, the CT PT Analyzer offers a wide range of features and functionalities that enable thorough examination of CTs and PTs. It is designed to meet the stringent requirements of the industry, ensuring reliable and accurate results.

 

Test Items


Equipment Description:

Tests for Current Transformer Tests for Potencial Transformer

1  Excitation curve and parameters test
2  Turns ratio test
3  Ratio and phase error test
4  Polarity mark check
5  Winding resistance measurement
6  Secondary loop burden measurement
7  Error line curve test for protection CT
8  Transient CT parameters test
9  CT nameplate guess
10  Saturation hysteresis loop curve measurement

1  Turns ratio test
2  Ratio error and phase angle error test
3  Polarity test
4  Secondary burden test
5  Winding resistance test

Applications of CT/ PT Analyzer:
 
1  CT nameplate check
2  CT parameters check in work burden
3  CT transient parameters analysis
4  CT ratio and phase error calibration
5  PT routine test

Technical Parameter


Technical Parameter

1.Test standards: IEC60044-1, IEC60044-6, IEC60044-2, IEC61869,IEC60044-5, C57.13
2.Power supply: AC220V±10%, 50/60Hz±10%
3.Voltage output: 0.1~180V (AC)
4.Current output: 0.001~5A(RMS)
5.Power output: 500VA
6.Maximum knee voltage measurement: 45KV
7.Current measurement:
   Range: 0~10A (automatically change range in 0.1/0.4/2/10A) 
   Error: <±0.1%+0.01%FS
8.Voltage measurement:
   Range: 0~200V (automatically change range in 1V/10V/70V/200V)
   Error: < ±0.1%+0.01%FS
9.Turns ratio measurement:
   Range:1~35000
   1~2000     error<0.05%
   2000~5000  error<0.1%
   5000~35000  error<0.2%
10.Phase measurement: error: ±2min;    resolution: 0.01min
11.Winding resistance measurement: 
    Range: 0~8kΩ (automatically change range in          2ohm/20ohm/80ohm/800ohm/8kohm)
    Error: < 0.2%RDG+0.02%FS
    Maximum resolution: 0.1mΩ
12.Temperature measurement:-50~100 Celsius degree; error<3 Celsius degree
13.CT Secondary burden:
    Range: 0~160ohm (automatically change range in 2ohm/20ohm/80ohm/160ohm)
    Error: <0.2%RDG+0.02%FS 
    Maximum resolution: 0.001ohm
14.PT Secondary burden:
    Range: 0~80kohm (automatically change range in 800ohm/8kohm/80kohm)
    Error :<0.2%RDG+0.02%FS 
    Maximum resolution: 0.1ohm
15.PT ratio measurement:
    Range: 1~35000
    1~10000 error<0.1%
    10000~35000 error<0.2%
16.PT ratio error measurement: Typical error <0.05%, Maximum Error<0.1%
17.PT phase angle measurement: maximum error < 3min
18.Make evaluation for test results according to selected standards
19.Make word report for test result
20.Make word reports one time for multi-group test records on the PC
21.Calculate the ratio errors and phase angle errors at rated burden and working burden in one time test
22.Compare excitation curves with saved excitation curves in the same window
23.Memory capacity: >1000 groups test results
24.Working condition: temperature: -10ºC~50ºC; moist: ≤90%
 
 

Testing Site

Automatic CT PT Analyzer CT Meter Transformer CVT Test Machine
Automatic CT PT Analyzer CT Meter Transformer CVT Test Machine

 

 

About Us

Automatic CT PT Analyzer CT Meter Transformer CVT Test Machine

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now

You Might Also Like

Diamond Member Since 2007

Suppliers with verified business licenses

Manufacturer/Factory, Trading Company
Registered Capital
100800000 RMB
Plant Area
>2000 square meters